KENR8601 89
Troubleshooting Section
Results:
•
OK – The diagnostic codes occur. The GSC+P
has not failed. The wire from G SC+P contact 35 to
terminal 2 of the alarm module is open or the wire
has failed.
Repair: Repair the wire or replace the wire.
STOP.
•
NOT OK – The diagnostic codes d o not occur. The
GSC+P may have failed.
Repair: The GSC+P may have failed. It is unlikely
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. During the
procedure, ensure that all cable probes are fully
seated and ensure that the probes are making
contact with the GSC+P pins. If the result is
repeated, replace the GSC+P. Refer to Testing and
Adjusting, “EMCP Electronic Control (Generator
Set) - Replace”.
STOP.