KENR8601 147
Troubleshooting Section
Repair: The GSC+P is operating correctly, and
the problem is in the wiring or the component that
is connected to the input of the circuit breaker
sensor. Use the FMI information and use the Close
Breaker Input System Schematic to find the exact
cause of the diagnostic code.
STOP.
•
NOT OK – The G SC+P does not issue the
diagnostic.
Repair: The GSC+P has faile d. Replace t he
GSC+P. Refer to Tes tin g and Ad jus tin g, “EM PC
Electronic Control (Generator Set) - Replace”.
STOP.
i02890927
GSC CID 1168 - FMI 03
SMCS Code: 445B-035
Conditions Which Generate This Code:
This dead bus sensor provides an additional
indication of the state of the bus. The bus can be
live or dead. The input of the dead bus sensor is
compared to the reading of the bus voltage, and the
diagnostics are produced if the measurements differ.
When the input of the dead bus sensor is inactive, the
input w ill float to approximately 10.5 DCV. An inactive
state indicates that the bus is live. When the input of
the dead bus sensor is active, the bus will be dead.
The possible cause of a CID 1168 FMI 03 is a short
from the input signal of the dead bus sensor to the
positive terminal of the battery (“BATT+”).
A CID 1168 FMI 03 is detected under the following
condition.
•
The v oltage of th e Phase A of the bus is less than
20% of the rated voltage and the input of the dead
bus sensor is floating. The voltage of the Phase A
is determined by the “BTB+” input to the GSC+P.
The GSC+P treats a CID 1168 FMI 03 as an alarm
fault. The dead b us paralleling function will be
stopped when this diagnostic code is detected. No
other synchronization processes will be affected.
Te st Step 1. CHECK THE INACTIVE
VOLTAGE LEVEL OF THE INPUT OF THE
DEAD BUS SENSOR .
A. Turn the Engine Control Sw itch (ECS) to STOP.
B. Locate the wire that is connecting pin 29 of
the GSC+ P to terminal “DBR-9” of the Dead
Bus Relay (D BR). Remove this wire at terminal
“DBR-9” of the DBR only. Pin 29 of G SC+P will
remain connected to the wire.
C. Use a cable probe to measure the voltage at pin
29 of the GSC+P.
Expected Result:
The voltage should measure 10.5 ± 1.0 DCV.
Results:
•
OK – The voltage level is 10.5± 1.0 DCV. Proceed
to Test Step 2.
•
NOT OK – The voltage level is not within the
correct range.
Repair: The GSC+P may have failed. It is u nlike ly
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer to Testing And
Adjusting, “EMCP Electronic Control (Generator
Set)-Replace”.
STOP.
Test Step 2. CHECK THE FUNCTION OF
THE BUS RELAY.
A. Reconnect the wire that is connecting pin 29 of
the GSC+P to the terminal “DBR-9” of the DBR.
B. Use a cable probe to monitor the voltage on pin
29 of the GSC+P.
C. Ensure that the bus is dead, or carefully
disconnec t po we r f ro m the re lay coil of the DBR.
Expected Result:
The voltage of pin 29 of the GSC+P should measure
0.0 ± 0.5 DCV.
Results:
•
OK – The voltage is 0.0 ± 0.5 DCV. Proceed to
Test S t e p 3.
•
NOT OK – T he voltage is incorrect.
Repair: The GSC+P has failed. Replace the
GSC+P. Refer to Testing and Adjusting, “EMPC
Electronic Control (Generator Set) - Replace”.
STOP.