KENR8601 37
Systems Operation Section
Note: Any active shutdown fault must be made
inactive in order to access service mode. When a
shutdown fault is active, a s hu tdown ind icator is
FLASHING. To temporarily change a shutdown fault
from an active shutdown fault to an inactive shutdown
fault, turn the ECS to the OFF/RESET position. To
permanently change a shutdown fault from an active
shutdown fault to an inactive shutdown fault, th e
shutdown fault must be no longer occurring. The fault
must be correcte d and the ECS must be turned to the
OFF/RESET position. If the jumper from terminal 6
toterminal9isnotinstalledontheECS,theGSC+P
does not power up in the OFF/RESET position and
any active shutdown fault m ust be corrected before
entering service m o de .
1. Turn the ECS to the STOP position in order to
shut down the engine. Enter service mode and
enter the password. “OP4” is showing on the lower
display. For more information, refer to Systems
Operation, “Password Entry OP3”.
2. Press “SCROLL UP” key again. “OP5-0” is
showing on the lower display.
3. Press “SELECT” key again. “P001” is showing on
the display. “P001” is followed by the value of the
setpoint.
4. Press the “SCROLL UP” key or the “SCROLL
DOWN” key. The next setpoint is showing with the
value of the setpoint. Repeat this step until the
desired setpoint is showing.
5. Press the “SELECT” key. The value of the setpoint
is fl ashing.
6. Press the “SCROLL UP” key or press the
“SCROLL DOWN” key in order to adjust the value
of the setpoint.
Note: Press and hold the appropriate “SCROLL”
key in order to rapidly scroll through a large range
of va lue s .
7. Press the “ENTER” key. The value of the setpoint
stops flashing. Repeat steps 4, 5, 6, and 7 until all
the desired setpoints are a djusted.
8. Press “EXIT” key. “OP 1” is showing on the lower
display.
9. Press “EXIT” key. The display will return to the
normal mode.