112 KENR8601
Troubleshooting Section
Repair: Repair the engine harness or replace the
engine harness.
STOP.
i02887983
GSC CID 0333 - FMI 03
SMCS Code: 4490-035
Conditions Which Generate This Code:
g01438113
Illustration 68
System Schematic For Alarm Module (ALM)
The Alarm Module (ALM) is available as an option.
The alarm module may be mounted on the front
panel. Also, the alarm module may be placed at
a distance from the control panel as a remote
annunciator. The ALM is used in order to satisfy the
requirements of the customer. The alarm module may
be used in order to satisfy National Fire Protection
Association (NFPA) requirements by annunciating
the presence of a diagnostic code.
The ALM communicates with the GSC+P by a serial
data link. When the data link malfunctions, all of the
indicators on the ALM, that are controlled by the data
link, flash at a rate of .5 Hz.
Note: The maximum number of the ALM or the
Customer Interface Modules (CIM) that may be
connected to the serial data link is equal to three.
The maximum distance between a module and the
GSC+P is 305 m (1000 ft). If these specifications are
not met, the ALM indicators may begin to flash. Also,
the G SC+P may show a CID 0333 FMI 03. If the
setup is not in c ompliance with the specifications,
reduce the n umber of modules a nd/or shorten the
distance to the modules.
Note: Diagnostic codes are created when the
harness connector is disconnected from the GSC+P
during these troubleshooting procedures. Clear these
created diagnostic codes after the particular problem
is corrected and the diagnostic code is cleared.