KENR8601 133
Troubleshooting Section
Results:
•
OK – The cable is firmly seated in the connector.
The clamp is in place. The cable is not damaged.
Reassemble the relay module to the GSC+P.
Proceed to Test Step 3.
•
NOT OK – One or more of the components are
damaged or the components are missing.
Repair: Replace the clamp if the clamp is missing.
If the cable is damaged, replace the GSC+P. Refer
to Testing and Ad ju stin g , “EMCP Electronic Control
(Generator Set) - Replace”.
STOP.
Te st Step 3. FUNCTIONAL CHECK OF
THE FCR
A. Turn the ECS to the OFF/RESET position.
B. Reconnect the battery negative cable.
C. Disconnect all wires from RM-15 and RM-4 of the
relay mod ule.
D. Rem o ve fuse “F3” from the r elay module.
E. At the relay module, measure the resistance from
RM-15toRM-4.Makeanoteoftheresistance
measurement.
F. Turn the ECS to the START posit ion and push
in the Emergency Stop Push Button (ESPB).
Measure the resistance from RM-15 to RM-4.
Make a note of the resistance measurement.
Expected Result:
The initial resistance m e asurement after removing
the wires and the fuse from the relay module
should be greater than 5000 ohms. The resistance
measurement should be less than 5 ohms when the
ECS is placed in the START position.
Results:
•
OK – The resistance measurements are correct.
The problem does not exist at this time. The
initial problem was probably caused by a poor
electrical connection or a short at one of the
harness connectors that was disconnected and
reconnected. Resume normal operation and watch
for a recurrence. STOP.
•
NOT OK – Either one of the resistance
measurements are NOT correct. The relay module
has failed.
Repair: Replace the relay module. Refer to Testing
And Adjusting, “Relay Module - Replace”.
STOP.
i02889590
GSC CID 0448 - FMI 12
SMCS Code: 4490-035-R7
Conditions Which Generate This Code:
g00721914
Illustration 74
System schematic for the programmable spare relays (“PSR1”
and “PSR2”)
The GSC+P u
ses the Programmable Spare Relay
(PSR) in orde r to activate the cus to mers’ e quipment.
Refer to Systems Operation, “Spare Input/Output
Programmi
ng OP6”.
Note: Whenever the GSC+P activates or the GSC+P
attempts
to activate th e PSR, K8 is shown on th e
lower display. When the PSR is not activated, K8 is
not shown.
The possible cause of a CID 0448 FMI 12 is an open
coil or a shorted coil of the PSR.
The system responses to these diagnostic codes are
listed b elow.
•
If a CID 0448 FMI 12 occurs and the PSR is active,
any customer’s equipment that is wired to RM-25
will be d
eactivated and any customer ’s equipment
that is w ire d to RM-26 will remain activated.