108 KENR8601
Troubleshooting Section
i02887665
GSC CID 0268 - FMI 02
SMCS Code: 4490-035
Conditions Which Generate This Code:
A portion of memory within the GSC+P stores the
setpoints of important generator set conditions. The
setpoints are listed below.
•
engine/generator setpoint programming OP5-0
•
protective relaying setpoints OP5-1
•
spare input/output programming OP6
•
voltmeter/ammeter setpoint programming OP8
The GSC+P detects a CID 0268 FMI 02 when the
setpoint data is invalid or the setpoint data is out
of range. After detecting a CID 0268 FMI 02, the
GSC+P sets the affected setpoints to the default
value. For more information regarding setpoints and
default values, refer to the topics that are listed below.
•
Systems Operation, “Engine/Generator
Programming OP5-0”
•
Systems Operation , “Protective Relaying
Programming OP5-1”
•
Systems Operation, “Spare Input/Output
Programming OP6”
•
Systems Operation, “Voltmeter/Ammeter
Programming OP8”
The possible cause of a CID 0268 FMI 02 is electrical
interference.
This procedure is designed to correct a n a ctive CID
0268 FMI 02 or the procedure is designed to correct
an inactive CID 0268 FMI 02. Clear the diagnostic
code from the fault log after troubleshooting is
complete.
The GSC+P treats a CID 0268 FMI 02 as an alarm
fault or th e GSC+P tre at s a CID 0268 FMI 02 as
a shutdown fault. The treatment depends on the
particular setpoint with bad data. The ring gear
teeth P0 09 se tpoint and t he engine overspeed P0 10
setpoints are treated as shutdown faults when the
particular data is corrupted. All other setpoints are
treated as alarm faults when the particular data is
corrupted.
Note: The GSC+P setpoints must be programmed in
the O FF/RESET position when a shutdown fault is
active. If the a larm for the fault indicator is FLASHING
the GSC+P can be programmed with the ECS in the
OFF/RESET position or the COOLD OW N/STOP
position.
CHECK THE SETPOINTS.
A. View the setpoints that are stored in the memory
of the GSC+P. Refer to Systems Operation,
“Engine/Generator Setpoint Viewing OP2-0”.
B. Also chec k Syst ems Ope ratio n, “Spare
Input/Output Programming (OP6)” and Systems
Operation, “Voltmeter/Ammeter Programming
(OP8)”.
C. Com pare the sto r ed setpoints to the specified
setpoints of the particular generator set.
Expected Result:
The stored setpoints and the specified setpoints
should match.
Results:
•
OK – All the setpoints match. Start the engine.
Check the upper display for a CID 0268 FMI
02. If the diagnostic code was inactive prior to
performing this procedure, then these steps should
have corrected the problem.
Repair: If the diagnostic code remains active,
The GSC+P may have failed. It is unlikely that
the GSC +P has faile d. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer toTesting And
Adjusting, “EMCP Electronic Control (Generator
Set)-Replace”.
STOP.
•
NOT OK – One or more of the setpoints do not
match.
Repair: Program the setpoints. Refer to the
following sections.
•
Systems Operation, “Engine/Generator
Programming OP5-0”
•
Systems Operation, “Protective Relaying
Programming OP5-1”
•
Systems Operation, “Spare Input/Output
Programming OP6”