KENR8601 113
Troubleshooting Section
One possible cause of a CID 0333 FMI 03 diagnostic
code is a short to the positive battery terminal
(“BATT+”).
The GSC+P treats a CID 0333 FMI 03 as an alarm
fault. Clear the diagnostic code from the fault log
after troubleshooting is complete.
Note: If a CID 0333 FMI 03 is active on the upper
display and no alarm module is installed, then
check the terminal strips on the subpanel for a
short. Perform the check from the signal wire to the
“BATT+”. Also, check the customers’ connection box
for a short from the alarm data signal wire to “BATT+”.
Te st Step 1. CHECK IF THE DIAGNOSTIC
CODE IS ACTIVE
A. TurntheEngineControlSwitch(ECS)tothe
OFF/RESET posit ion an d th en turn the ECS to
the STOP position.
B. Press the “Alarm Codes” key.
C. Observe the upper display for a CID 0333 FMI 03.
The diagnostic c ode is a ctive if the upper display
shows a CID 0333 FMI 03.
D. If the diagnostic code is not showing, enter the
service mode and view the fault log. Check the
upper display if the diagnostic code is active.
Expected Result:
A CID 0333 FMI 03 is active.
Results:
•
OK – A CID 0333 FMI 03 is active. Proceed to
Test Step 2.
•
NOT OK – A CID 0333 FMI 03 has not occurred.
The diagnostic code is NOT active. STOP.
Test Step 2. CHECK FOR SHORTED
DATA LINK WIRE
A. Disconnect the cable from the negative battery
terminal “(BATT-)” or open the optional battery
disconnect switch.
B. Disconnect both ends of the data link wire. The
following contacts are the ends of the data link
wire: pin 35 of the GSC+P and terminal 2 o f the
alarm module.
C. Measure the resistan ce between the data link w ire
and “BATT+” terminal of the GSC+P.
Expected Result:
The resistance should be greater than 5000 ohms.
Results:
•
OK – T he resistance is correct. Proceed to Test
Step 3.
•
NOT OK – The resistance is NOT greater than
5000 ohms. The data link wire is faulty.
Repair: Refer to the system schematic in order
to troubleshoot the harness wiring and repair the
harness wiring that has failed between the ALM
and the GSC+P. Refer to Testing and Adjusting,
“Schematics and Wiring Diagrams” for further
information.
STOP.
Test Step 3. CHECK THE ALARM
MODULE
A. The cable on the “BAT T -” terminal will remain
disconnected or the optional battery disconnect
switch is open.
B. Meas ure the resistan ce from term ina l 2 of the
alarm module to “BATT+”.
Expected Result:
The resistance should be greater than 5000 ohms.
Results:
•
OK – The resistance is greater than 5000 ohms.
Proceed to Test Step 4.
•
NOT OK – The resistance is NOT greater than
5000 ohms. The alarm module has failed.
Repair: Replace the alarm m odule.
STOP.
Test Step 4. CHECK THE GSC+P.
A. The data link wire remains disconnected.
B. Connect the cable on the “BATT-” terminal of the
battery or close the optional battery disconnect
switch.
C. Turn the engine control switch to the STOP
position.
D. Check for an active CID 0333 FMI 03 diagnostic
code on the GSC+P.
Expected Result:
The diagnostic code is NO longer active.