120 KENR8601
Troubleshooting Section
Expected Result:
The voltage is approximately 5 ± 1.0 DCV.
Results:
•
OK – The voltage is approximately 5 ± 1.0 DCV.
The voltage is correct. Proceed to Test Step 2.
•
NOT OK – The voltage is NOT approximately 5 ±
1.0 DCV. T he voltage is NOT correct. The GSC+P
has failed.
Repair: It is unlikely th at the GSC+P has failed.
Exit this diagnostic code procedure and repeat
the CID 0334 FMI 04 diagnostic code procedure
again. If the cause of the failure is still unknow n ,
then replace the GSC+P.
STOP.
Te st Step 2. CHECK FOR A SHORT TO
“BATT-” IN THE WIRING OF THE SPARE
OUTPUT
A. Disco n nect the “BATT-” terminal from the battery.
B. Disconnect the wire from pin 36 of the GSC+P.
C. Disconnect the other end of the wire at the
customers’ device.
D. Measure the resistance between the wire that wa s
disconnected from pin 36 of the GSC+P and the
“BATT-” contact of the GSC+P.
Expected Result:
The resistance is greater than 5000 ohms.
Results:
•
OK – The resistance is greater than 5000 ohms.
The circuit is correct. Proceed to Test Step 3.
•
NOT OK – The resistance is less than 5000 ohms.
The circuit is not correct. The spare output is
shortedto“BATT-”.
Repair: Repair the wiring of the spare output.
STOP.
Te st Step 3. RECONNECT TO
CUSTOMERS’ DEVICE
A. Reconnect the wire to the customers’ device.
B. Reconnect the wire that was disconnected from
contact 36 to the GSC+P.
C. Turn the ECS to STOP and check if the diagnostic
code is still active.
Expected Result:
The diagnostic code is not active.
Results:
•
OK – The diagnostic code is not active. It is likely
that the problem was in the wiring harness or the
problem is intermittent.
Repair: Check the wiring between the GSC+P
and the customer device for problems. Repair the
wiring or replace the wiring if a problem is found.
Watch for a recurrence of the diagnostic code.
STOP.
•
NOT OK – The diagnostic code is still active.
There may be a problem with the customer device.
Repair: The customer device may have failed.
Refer to the customers’ documentation and the
dealers’ documentation for the device.
STOP.