KENR8601 159
Troubleshooting Section
5. Check the wiring to the corresponding spare fault
input for an unwanted short. The short can be
to the negative battery terminal (“BATT-”). Also,
The short can be to the positive battery terminal
(“BATT+”).
i02893378
Troubleshooting Dedicated
Shutdown Indicators
SMCS Code: 4490-035-IND
g00688554
Illustra
tion 85
Display Area Of Generator Set Control + (G SC+P)
(1) Dedicated shutdown indicators
(2) Spare fault indicators
(3) Fault shutdown indicator
(4) Fault alarm indicator
(5) Upper display
(6) Lower display
(7) Keypad
The dedicat
ed shutdown indicators show the system
that is respon sible for an en gine shutdown. The
symbol and nomenclature that is located next to the
indicator
identifies the responsible system. Dedicated
shutdown faults are activated automatically by
the GSC+P. Dedicated shutdown faults depend
on c erta i
n setpoints. When the GSC+P decides
that operating conditions are critical, the GSC+P
FLASHES the corresponding shutdown indicator.
Then, the
GSC+P shuts down the engine. The
GSC+P does not record dedicated shutdown faults
in the fa ult log.
The dedicated shutdown indicators (faults) are listed
below.
•
Low Oil Pressure
•
Emergen
cy Stop
•
High Water Temperature
•
Engine Overspeed
•
Overcrank
To find the cause of a dedicated shutdown fault,
perform the correct procedu re.
i02893424
Indicator for Emergency Stop
SMCS C ode: 4490-035-IND
System Operation Description:
In order to find the cause of an emergency stop
shutdown, perform the following procedure.
Tes t Step 1. CHEC K THE EMERGENC Y
STOP PUSH BUTTON (ESPB).
A. Pull out the ESPB in order to deactivate the push
button. Some versions of ESPB must be turned
clockwise before you pull out the ESPB.
B. Turn the Engine Con trol Switch (ECS) to the
OFF/RESET position and then turn the ECS to
the COOLDOWN/STOP position.
Expected Result:
The ESPB should pop out. The emergency stop
indicator should be OFF.
Results:
•
OK – The system is operating correctly. The
problem may be intermittent.
Repair: Check the harness and all electrical
connections of the ESPB circuit. R efer to Testing
and Adjusting, “Electrical Connector - Inspect”.
STOP.
•
ESPB NOT POPPED OUT – The ESPB does not
pop out.
Repair: Replace the ESPB.
STOP.
•
ESPB OUT, IND ICATOR FLASHIN G – The ESPB
pops out and the emergency stop indicator is
FLASHING. Go to 2.