192 KENR8601
Testing and Adjusting Section
Table 29
Service Table - Record Of Setpoint Values
OP5-3 Setpoints
- Paralleling P rogramming
Generator Description : Site, Serial No., EMCP II+ Part No., etc..
Setpoint Specied Value
Actual Value
Setpoint
Description
Possible Values
Default Value
P301
Synchronization
Enable
0 - disabled
1-Woodward
0
P302
Breaker Coil Time
Limit
0.2 to 5.0 secon
ds in
increments of 0.1 second
1.0 second
P303 Voltag e Limit
Enable
0 - disabled
1 - enabled
1
P304 Voltag e Limit
1% to 15 % in increments
of 1%
1%
P305
(1)
Phase Toleran
ce
Limit
1to25degrees
in
increments of 1 degree
5degrees
P306
(1)
Dwell Time 0.1 to 1.0 seconds in
increments o
f 0.1 second
0.5 second
P307
(1)(2)
Speed Control
Gain
0.0% to 100.0% in
increments of 0.1%
50.0%
P308
(1)(2)
Speed Contro
l
Rate
0.0% to 100.0
%in
increments of 0.1%
50.0%
P309
(1)(2)
Speed Control
Damping
0.0% to 100.0% in
increments of 0.1%
0.0%
P310 Dead Bus
Closure Enable
1 - enabled
(3)
0 - disabled
0
P311 Dead Bus Limit
5% to 50% in in
crements of
1%
20%
P312
Dead Bus On
Time Delay
0 to 120 seco nds in
increments
of 1 second
0 seconds
P313 Frequency Match
Notification Time
5to1000secondsin
increments of 1 seconds
20 seconds
P314 Maximum
Synchronization
Time
5to1000secondsin
increments of 1 secon d
30 seconds
(1)
P305, P306, P307, P308, and P309 can be adjusted to precisely match individual engine response and breaker closure characteristics
using OP11 - Synchronization Setpoint Tuning.
(2)
The GSC+P uses P-I-D (proportional-integral-derivative) control to accomplish synchronization qu ickly and smoothly. The P parameter, I
parameter, and D parameter are independantly controlled by setpoints P307, P308, and P309 respectively. Adjusting a ny one of these
setpoints will not affect the other two settings. For more information, see Systems Operation, “Synchronization Mode” Setpoint Tuning.
(3)
Dead bus closure will only work in the automatic mode, NOT in permissive mode or semi automatic mode.