KENR8601 87
Troubleshooting Section
i02885949
Indicators of Alarm Module
or Remote Annunciator Are
Constantly Flashing
SMCS Code: 4490-035
System Operation Description:
g01438113
Illustration 56
System schematic for Alarm Module (ALM)
The fault indicators of the remote annunciator or the
control panel alarm module that are controlled by
the data link will flash at a rate of 0.5 H z (every t wo
seconds).
There are several possible causes when the
indicators of the alarm mo du le are flashing. Before
performing the test procedure, review the following
requirements for the alarm module .
•
Check The Generator Set control + Paralleling
(GSC+P) For Diagnostic Codes. If a CID 333 FMI
03 or CID 333 FMI 04 diagnostic code is active or
if the codes are contained in the fault log, perform
those procedures first.
•
Verify The Number Of Modules. A maximum of
three modules can be connected to the GSC+P
data link for th e a larms.
•
Verify That All Remote Modules Are Powered.
If multiple module s are co n ne cted to a GSC+P,
ALL of the modules must be powered up. If a
module is not powered and the po sit ive battery
wire “BATT+” is disconnected or if the ground wire
is disconnected, the wire on terminal 2 must be
disconnected as well.
•
Verify The Length Of The Wire. The maximum
length of the wires between the GSC+P and a
remote annunciator is 304 m (1000 ft). Note: The
actual length of the wire c an be considerably
longer than the physical distance between the two
modules.