KENR8601 85
Troubleshooting Section
Repair: Program the setpoints in OP8 to match the
values on the ATB+. Refer to System O peration,
“Voltmeter/Ammeter Programming OP8”.
STOP.
Te st Step 10. INACCURATE POWER
CONSUMPTION IS DISPLAYED ON THE
GSC+P.
A. Start the genset.
B. Check for inaccurate power factors for each
individual phase by depressing the “Power Key”
for more than 5 seconds.
Expected Result:
The power factors for each phase should be accurate.
Results:
•
OK – The power factors for each phase are
accurate.
Repair: The GSC+P may have failed. It is unlikely
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer to Testing And
Adjusting, “EMCP Electronic Control (Generator
Set) - Replace”.
STOP.
•
NOT OK – The power factors for each phase are
inaccurate. Proceed to Test Step 11.