KENR8601 137
Troubleshooting Section
i02889768
GSC CID 0590 - FMI 09
SMCS Code: 1901-035
Conditions Which Generate This Code:
The CID 0590 failure means that the engines’
Electronic Control Module (ECM) has stopped
responding to the periodic requests for information
from the GSC+P.
CHECK THE CAT D ATA LINK
A. TurntheEngineControlSwitch(ECS)to
OFF/RESET position.
B. Disconnect the pins 19 and 20 of the CAT data
link from the GSC+ P.
C. Disconnect the pins 13 and 14 of the CAT data
link from t he ECM.
D. Measure the resistance between pin 19 of the
GSC+P and pin 14 of the ECM.
E. Measure the resistance between pin 20 of the
GSC+P and pin 13 of the ECM.
Expected Result:
The resistance for both measurements is less than
5ohms.
Results:
•
OK – The resistance for both m easurements is
less than 5 ohm s. The circ uit is correct. The ECM
has failed.
Repair: It is unlikely that th e ECM has fa ile d.
Clear the diagnostic code from the fault log after
troubleshooting is complete. The GSC+P is usually
programmed to treat a CID 590 diagnostic code as
an “alarm fault”. Setpoint P0 4 is 0. I f th e GSC+P is
programmed to treat this code as a shutdown fault,
setpoint P04 is 1. Then, it is not necessary to press
the “alarm codes” key in order to see the diagnostic
code. The diagnostic code is automatically shown
on the upper display.
STOP.
•
NOT OK – The resistance for both measurements
is greater than 5 o hms. T he circuit is not corre ct.
Repair: Repair the wiring of the C AT data link or
replace the wiring of the C AT data link.
Clear the diagnostic code from the fault log after
troubleshooting is complete. The GSC+P is usually
programmed to treat a CID 590 diagnostic code as
an “alarm fault”. Setpoint P04 is 0. If the GSC is
programmed to treat this code as a shutdown fault,
setpoint P04 is 1. Then, it is not necessary to press
the “alarm codes” key in order to see the diagnostic
code. The diagnostic code is automatically shown
on the upper display.
STOP.
i02890100
GSC CID 0770 - FMI 09
SMCS Code: 1926-035
Conditions Which Generate This Code:
g01439077
Illustration 76
System schematic for CCM data link
Note: When a Customer Communication Module
(CCM) is connected to a single genset, the positive
battery terminal “BATT+” is connected directly to
TS-BATT+ . When a CCM is connected to mu ltip le
gensets, connect the CCM to TS-73, and ensure that
a wire is added between TS-73 on all generator sets.
On gensets that are equipped with a CCM, the
GSC+P uses the “CCM data link” to communicate
with the CCM.
The CCM data link consists of two wires that connect
the GSC+P to the C CM.
The possible causes of a CID 0770 FMI 09 are listed
below.
•
A short to “BATT+” from either one of the two
connector pins, 21 or 22
•
A short from the negative battery terminal (“BATT-”)
to either of the two connector pins, 21 or 22