126 KENR8601
Troubleshooting Section
Repair: Replace the relay module. Refer toTesting
And Adjusting, “Relay Module - Replace”.
STOP.
i02888433
GSC CID 0442 - FMI 12
SMCS Code: 4490-035-R7
Conditions Which Generate This Code:
The GSC+P uses the G enerator Fault Relay (GFR)
in order to activate the circuit breaker for the shunt
trip coil during a shutdown fault. The GFR is located
within the relay module. The circuit breaker is located
in the generator housing.
Note: Whenever the GSC+P activates or the GSC+P
attempts to activate the GFR, “K2” is shown on the
lower display. When the GFR is not activated, “K2” is
not shown.
The possible cause of a CID 0442 FMI 12 is an open
coil or a shorted coil of the G FR.
The system response to this diagnostic code is listed
below.
•
When a CID 0442 FMI 12 occurs and the GFR
is activated, the diagnostic code will not have an
effect on the s ystem . The system is not affected
because the circuit breaker is already open and
shutdown mode is functioning. The generator is
already off-line.
•
If a CID 0442 FMI 12 occurs and the GFR is not
activated, the GFR cannot activate the shunt trip
coil of the circuit breaker when a shutdown fault
occurs.
The GSC+P treats a CID 0442 FMI 12 as an alarm
fault. Active alarm faults are shown on the display
when the “Alarm Codes” key is pressed. The ECS
must be in any position except the OFF/RESET
position. Clear the diagnostic code from the fault log
after troubleshooting is complete.
This troubleshooting procedure is for an active CID
0442 FMI 12 or the troubleshooting procedure is for
an inactive CID 0442 FMI 12.
Te st Step 1. CHECK T HE STATUS OF THE
DIAGNOSTIC CODE.
A. Turn the EC S to the OFF/RESET position and
then turn the ECS to the STOP position.
B. Press the “Alarm Codes” key.
C. Observe the upper display. Check that the CID
0442 FMI 12 is active.
D. If the diagnostic code is not active, enter the
Service Mode. View the fault log for a OP1. Check
that the diagnostic code is inactive.
Expected Result:
A CID 0442 FMI 1 2 is displayed as an active
diagnostic code or CID 0442 FMI 12 is displayed as
an inactive diagnostic code.
Results:
•
OK – The CID 0442 FMI 12 is active or the CID
0442 FMI 12 is inactive. Proceed to Test Step 2.
•
NOT OK – The CID 0442 FMI 12 has not occurred.
The diagnostic code is not active and the diagnostic
code is not inactive. STOP.
Tes t Step 2. CHECK THE INTERNAL
CABLE OF THE RELAY MODULE.
Note: Only open the relay module in a dry
environment. If the inspection and repair takes
more th an approxi mately twenty minutes replace
the desiccant bag in the GSC+P housing. Refer to
Testing And Adjusting, “Relay Module - Replace”.
A. Turn the ECS to the OFF/RESET position.
B. Disconnect the negative battery cable.
C. Temporarily, remove the relay module from the
GSC+P. Refer to Testing And Adjusting, “Relay
Module - Replace”.
D. Check the cable that attaches the relay module
to the GSC+P.
Expected Result:
The cable should be firmly seated in the connector.
The clamp should be in place. The cable should not
be damaged.
Results:
•
OK – The cable is firmly seated in the connector.
The clamp is in place. The cable is not damaged.
Reassemble the relay module to the GSC+P.
Proceed to Test Step 3.
•
NOT OK – One or more of the components are
damaged or the components are missing.