KENR8601 39
Systems Operation Section
(Table 6, contd)
OP5-0 S etp oints
- Engin e/Generator Programming
(1)
Setpoint
Name Description
Range Of Value Controller Default
P014
(3)
Low Oil Pressure
Shutdown At Idl
e
Speed
Oil pressure used by the GSC+P to declare
that a low oil pr
essure shutdown fault e xist
with the engine at idle speed (the engine must
have be en running for at least nine seconds
and the engine
speedmustbelessthanoil
step speed).
20 to 336 kPa
(3 to 49 psi)
in increments of 1
70 kPa (10 psi)
P015
(4)
High Water
Temperature
Shutdown
Coolant temperature used by the GSC+P to
declare a high coolant temperature shutd own
fault exists (after a 10 second delay).
85 to 123°C
(185 to 253°F)
in increments of 1
107°C (225°F)
P016 Low Water
Temperature
Alarm
Coolant temperature used by the GSC+P to
declare that a
low temperature alarm fault
exists (after a 2 seco nd delay). (De termined
by application or custo mer.)
0to36°C(32to97°F)
in increments
of 1
21°C (70°F)
P017
Total Cycle
Crank Time
Cycle crank time used by the GSC+P to
declare that an overcrank fault exists.
(Determined by application or customer.)
5 to 360 secon
ds
in increments of 1
90 seconds
P018
Cycle Crank
Time
Amount of tim
e the GSC+P cranks and
then rests the starting motor during a single
crank cycle. Determined by application of
customer.)
5 to 300 seconds
in increments of 1
10 seconds
P019
Cooldown Time Amount of time the GSC+P allows the engine
to run after a normal shutdown is initiated.
(Determined by application or customer.)
0to30minutes
in increments of 1
5 minutes
P020
(5)
AC Voltage Full scale AC voltage of the generator. The
GSC+P measures the AC voltage and shows
it on the dis
play. (Determined by application
or customer.)
700, 150, 300, 500,
600, 750, 3.0k, 4.5k,
5.25k, 9.0k, 15.0k,
18.0k, 30.0k
700
P021
AC Current Full
Scale
AC current full scale is the ratio of the Current
Transformer s (CT) bas ed on a 5A secon dary.
It does not represent the maximum AC current
of the generator. The GSC+P me asures the
current and shows it on the display.
75, 100, 150, 200, 300,
400, 60 0, 8
00, 100 0,
1200, 1500, 200 0,
2500, 3000, 4000A
600A
P022
(6)
GSC+P Engine
Number
Informs other devices on the CAT Data Link
(for example, CCM) o f the engine number
for the GS
C+P (Determined by application
or customer).
01 through 08 01
P023 Engine Type
Identifies the engi ne as a Mechanical Unit
Injector (MU I) diesel, spark ignited (gas), or
Electronic Unit Injector (EUI) diesel engine.
0-MUIdiesel
1-Gas
2-EUIdiesel
P024
(7)
Crank Time
Delay
Amount of time the GSC+P delays activation
of the Fu
el Control Relay (FCR) during a
crank cycle. This setpoint is for gas engines
only. (Determined by application or customer.)
0to20seconds
in increments of 1
5 seconds
P025
Oil Temperature
Sensor Installed
Tel l s wh
ether or not the optional engine
oil tempe rature sensor is installed on the
generator set.
0 - gener
ator sets
without an oil
temperature sensor
1 - gener
ator sets with
an oil temperature
sensor
0
P026
High Oil
Temperature
Shutdown
Oil temperature used by the GSC+P to
declare a high oil temperature shutdown fault
exists(aftera10seconddelay).
85 to 123°C
(185 to 253°F)
in increments of 1
107°C (225°F)
(continued)