KENR8601 61
Systems Operation Section
i02899086
SP Fault Codes
SMCS Code: 4490
SP fault codes are associated with the spare inputs.
SP fault codes are either alarm faults or shutdown
faults. The four spare inputs and a spare output are
provided in order to meet the needs of the customer.
The spare inputs are programmable to active state,
severity, and delay time. Refer to System Operation,
“Spare Input/Output Programming OP6”. The spare
inputs and the corresponding SP fault codes are
referred to as SP1, SP2, SP3, and SP4.
Alarm Mode Sequence Of Operation – The
following procedure happens when a fault occurs
in a spare input (the active input ) and the fault is
programmed as an alarm fault.
1. TheGSC+Pwaitsforthetimedelay.
2. The fault alarm indicator FLASHES .
3. When the alarm codes key is pressed, the
corresponding SP1, SP2, SP3, or SP4 is code
shown on the upper display.
4. The engine continues to run or the engine is able
to start.
Shutdown Mode Sequence Of Operation – The
following sequence happens when a fault occurs
in a spare input and the fault is programmed as a
shutdown fault.
1. TheGSC+Pwaitsforthetimedelay.
2. The fault shutdown indicator FLASHES.
3. The corresponding code SP1, SP2, SP3, or SP4
is immediately SHOWN on the upper display of
the GSC+P.
4. The engine is shut down or the engine is disabled
from starting.
Note: Spare faults are not logged into the G SC+P
fault log.
Note: Spare faults that are programmed to shutdown
are ig n ore d b y th e G S C+P when the engine speed is
less than crank terminate speed.
i02899114
Diagnostic Codes
SMCS Code: 4490
Diagnostic fault codes are associated with failed
electrical components or circuits. These components
or circuits provide information to the GSC+P or the
components or circuits receive information from the
GSC+P. The d iagnostic fault codes are designated
as alarm faults or shutdown faults. Refer to System
Operation , “Shutdown Mode” for more information.
Refer to System Operation, “Alarm M ode”for m ore
information.
Alarm Mode Sequence Of Operation – When an
alarm fau lt occurs, the GSC+P performs the fo llo wing
steps.
•
The GSC+P activates the alarm mode.
•
The fault alarm indicator FLASHES.
•
When the alarm codes key is pressed, the
corresponding diagnostic code is shown on the
upper display.
•
The engine continues to run or the engine is able
to start.
Shutdown Mode Sequence O f Operation – When
a shutdown fault occurs, the GSC+P performs the
following steps.
•
The GSC+P activates shutdown mode.
•
The fault shutdown indicator FLASHES.
•
The corresponding diagnostic code (CID FMI) is
immediately shown on the upper display.
•
The engine is shut down or the engine cannot be
started.
The diagnostic fault code (CID FMI) closely identifies
the cause of the fault. Each diagnostic fault consists
of two identifiers and an indicator. The identifiers
are shown on the upper display. Service personnel
interpret the identifiers in order to assist with
troubleshooting.
The indicators are listed below.
Component Identifier (CID) – The CID is a three
digit code. The code that is indicated corresponds
to a faulty component. The CID is shown on the
upper display. For example if the Engine Magnetic
Pickup (MPU) is faulty then “190”would be displayed.
Refer to the Testing And Adjusting, “Diagnostic Fault
Codes” for a list of CID codes .