KENR8601 155
Troubleshooting Section
Expected Result:
The voltage should be equal to the voltage measured
in Test Step 2 divided by 15 ± 2 % (14.7 to 15.3).
Results:
•
OK – The voltage is correct. CID 1170 FMI 2 is
still active.
Repair: The GSC+P may have failed. It is unlikely
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer to Testing And
Adjusting, “EMCP Electronic Control (Generator
Set) - Replace”.
STOP.
•
NOT OK – The voltage is not correct. The wiring
harness has failed between the BTB + and the
generator.
Repair: The wiring harness has failed between the
BTB + and the generator. Repair the wiring harness
or replace the wiring harness. Use the System
Schematic for the BTB + and the AC schematic in
the Testing And Adjusting, “Schematics And Wiring
Diagrams” section.
STOP.