KENR8601 125
Troubleshooting Section
This troubleshooting procedure is for an active CID
0441 FMI 12 code. Also, this procedure is for an
inactive CID 0441 FMI 12 code.
Te st Step 1. CHECK T HE STATUS OF THE
DIAGNOSTIC CODE.
A. Turn the EC S to the OFF/RESET position and
then turn the ECS to the STOP position.
B. Press the “Alarm Codes” key.
C. Ob serve the upper display. Check that the CID
0441 FMI 12 is active.
D. If the diagnostic code is not active, enter the
Service Mode. View the fault log for a OP1. Check
that th e diagnostic code is in active.
Expected Result:
A CID 0441 FMI 12 is dis pla yed as an a ctive
diagnostic code or CID 0441 FMI 12 is displayed as
an inactive diagnostic code.
Results:
•
OK – The CID 0441 FMI 12 is active or the CID
0441 FMI 12 is inactive. Proceed to Test Step 2.
•
NOT OK – The CID 044 1 FMI 12 has not occurred.
The diagnostic c ode is not active and the diagnostic
code is not inactive. STOP.
Te st Step 2. CHECK THE INTERNAL
CABLE OF THE RELAY MODULE.
Note: Only open the relay module in a dry
environment. If the inspect ion and repair t akes more
than approximately twenty minutes replace the
desiccant bag in the GSC+P housing. Refer toTesting
And Adjusting, “Relay Module - Replace”.
A. Turn the ECS to the OFF/RESET position.
B. Disconnect the negative battery cable.
C. Temporarily, remove the relay module from the
GSC+P. Refer toTesting And Adjusting, “Relay
Module - Replace”.
D. Check the cable that attaches the relay module
to the GSC+P.
Expected Result:
The cable should be firmly seated in the connec tor.
The c lamp should be in place. The cable should not
be damaged.
Results:
•
OK – The cable is firmly seated in the connector.
The clamp is in place. The cable is not damaged.
Reassemble the relay module to the GSC+P.
Proceed to Test Step 3.
•
NOT OK – One or more of the components are
damaged or the components are missing.
Repair: Replace the clamp if the clamp is missing.
If the cable is damaged, replace the GSC+P. Refer
toTesting an d Adjusting, “EMCP E lectronic C ontrol
(Generator Set) - Replace”.
STOP.
Tes t Step 3. PERFORM A FUNCTIONAL
CHECK O N THE EGR.
A. Turn the ECS to the OFF/RESET position.
B. Reconnect the negative battery cable.
C. Disconnect all wires from RM-13 and RM-14 of
the relay module.
D. At the relay module, measure the resistance from
RM-13 to RM-14. Make a note of the resistance
measurement.
E. Start the engine and run the engine. M ake sure
that the engine oil pressure is greater than the
setpoint for low oil pressure shutdown at idle
speed (P014).
F. At the relay module, measure the resistance from
RM-13 to RM-14. Make a note of the resistance
measurement.
Expected Result:
The initial resistance measurement after removing
the wires from the relay module should be 5000
ohms. The resistance measurement should be 5
ohms after exceeding the setpoint for low oil pressure
shutdown at idle speed.
Results:
•
OK – The resistance measurements are correct.
The problem does not exist at this time. The
initial problem was probably caused by a poo r
electrical connection or a short at one of the
harness connectors that was disconnected and
reconnected. Resume normal operation and watch
for a recurrence. STOP.
•
NOT OK – Either one of the resis tance
measurements are NOT correct. The relay module
has failed.