138 KENR8601
Troubleshooting Section
Note: The GSC+P cannot detect an open in the
circuit of the CCM data link. The GSC+P treats a
CID 0770 as an alarm fault. Active a larm faults are
shown on the display when the “Alarm Codes” key
is pressed and the Engine Control Switch (ECS)
is in any position except the OFF/RESET position.
Troubleshoot and repair the wiring. Refer to Testing
and Adjusting, “Schematics and Wiring Diagrams”.
Clear the fault from the fault log after troubleshooting
is com plete.
Te st Step 1. CHECK THE CCM FOR A
SHORT TO “ BATT+”
A. Turn the ECS to the OFF/RESET position.
B. Disconnect the “BATT+” and “BATT-” battery leads
from the battery.
C. Measure the resistance between pin 21 and
“BATT+”.
D. Measure the resistance between pin 22 and
“BATT+”.
Expected Result:
The resistance is greater than 5000 ohms for both
cases.
Results:
•
OK – The resistance is greater than 5000 ohms
for both cases. The circuit is correct. Proceed to
Test Step 2.
•
NOT OK – The resistance is less than 5000 ohms.
The circuit is not corre ct.
Repair: The“CCMdatalink”isshortedto“BATT+”.
Repair the wiring or replace the wiring.
The G SC+P treats a CID 770 as an alarm fault.
Active alarm faults are shown on the display when
the alarm codes k ey is pressed and the ECS is not
in the OFF/RESET position. Clear the fault from
the fault log after the troubleshooting is complete.
STOP.
Te st Step 2. CHECK THE CCM FOR A
SHORT TO “BATT-”
A. Turn the ECS to the OFF/RESET position.
B. Disconnect the “BATT+” and “BATT-” battery leads
from the battery.
C. Measure the resistance between pin 21 and
“BATT-”.
D. Measure the resistance between pin 21 and
“BATT-”.
Expected Result:
The resistance is greater than 5000 ohms for both
cases.
Results:
•
OK – The resistance is greater than 5000 ohms
for both cases. The circuit is correct.
Repair: The failure is intermittent. The probable
cause is a poor electrical connection. Check the
wiring and repair the wiring, as needed.
The G SC+P treats a CID 770 as an alarm fault.
Active alarm faults are shown on the display when
the a larm codes key is pressed and the ECS is
in any position except the OFF/RESET position.
Clear the diagnostic code from the fault log after
the tro ub le sh ooting is complete.
STOP.
•
NOT OK – The resistance is less than 5000 ohms.
The circuit is not correct.
Repair: The CCM data link is shorted to “BATT-”.
Repair the wiring or replace the wiring.
The G SC+P treats a CID 770 as an alarm fault.
Active alarm faults are shown on the display when
the a larm codes key is pressed and the ECS is
in any position except the OFF/RESET position.
Clear the diagnostic code from the fault log after
the tro ub le sh ooting is complete.
STOP.
i02890528
GSC CID 0858 - FMI 03
SMCS Code: 1420-035
Conditions Which Generate This Code:
The close breaker control output drives the Circuit
Breaker Permissive Relay (CBPR). The generator
circuit breaker connects the generator to the bus.
The inactive level of this output is floating. The
voltage range may be from 5.2 DCV to the voltage of
the positive battery terminal “(BATT+)”. The active
voltage level is at the voltage of the negative battery
terminal (“BATT-”).