48 KENR8601
Systems Operation Section
TheGSC+Pmustbeprogrammedtoacceptthe
condition that triggers the spare output to the active
state. A large selection of trigger conditions is
available to activate the spare output. Setpoint SP14
is used for the programming of the trigger condition.
Table 9 describes the setpoints.
Note: A common use of the spare output is activating
the shunt trip coil of the AC circuit breaker during
engine cooldown.
Note: The GSC+P diagnoses a fault in the spare
output circuit. Refer toCID 334 in the topic Testing
And Adjusting Section, “Diagnostic Fault Codes” for
more information.
Programmable Spare Relay
Outputs
g004098
83
Illustration 44
Programmable S pare Relay (PSR)
Note: On
EMCP II+P pa n els , the PSR is not available
for use by the customer. The EMCP II+P uses this
output.
The (PSR) should respond to a selected trigger
condition. The response and the trigger condition
are prog
rammable. The programmable spare relay
(K8) is located in the relay module on the rear of the
GSC+P. RM-25 is the termination for the normally
open co
ntacts of the P SR. RM-26 is the termination
for the normally closed contacts of the PSR.
When the outputs are triggered, the GSC+P must be
programmed to decide whether the outputs of the
PSR are active or inactive. In an active state, the
normally open contacts will close and the normally
closed contacts will open. Setpoint SP15 is used to
program the active state of the spare relay output.
The setpoint is described in 9.
The GSC+P must be programmed for the c ondition
that triggers the output of the program mable s pare
relay to the active state. A large selection of trigger
conditions is available to activate the output of
the spare relay. Setpoint SP16 is used for the
programming of the trigger condition. Th e setpoint is
described Table 9.
Note: The GSC+P diagnoses a fault in the output
circuit of t he prog ram mable sp are relay. For
more information, refer to Testing And Adjust ing ,
“Diagnostic Fault Codes”.
Procedure For Spare Input/Output
Programming
Note: Service Mode cannot be entered when the
ECS is in the AUTO position.
Note: Any active shutdo w n fault must be made
inactive in order to access service mode. A shutdown
fault is ac tive when any shutdown indicator is
FLASHING. To temporarily change a shutdown fault
from an active shutdown fault to an inactive shutdown
fault, turn the ECS to the OFF/RESET position. To
permanently change a shutdown fault from an active
shutdown fault to an inactiv e shutdow n fault, the
shutdown fault must no longer be occurring. The fault
must be corrected and the ECS must be turned to the
OFF/RESET position. If the jumper from terminal 6
to terminal 9 is not installed on the ECS, the G SC+ P
does not power up in OFF/RESET and any active
shutdown fault must be corrected before entering
Service Mode.
1. Shut down the engine by turning the ECS to the
STOP position. Enter Service Mode and enter the
password. “OP 4” is showing on lower display.
For more information, refer to Systems Operation,
“Procedure To Enter The Password”.
2. Press the “SCROLL UP” key three times. “OP 6”
is showing o n the lower display.
3. Press the “SELECT” key. SP01 is showing. SP01
is followed by the value of the setpoint.
4. Press the “SCROLL UP” or the “SCROLL DOWN”
key. The nex t se tpoint and the value for the
setpoint is showing. Repeat this step until the
desired value is showing.