KENR8601 55
Systems Operation Section
Note: The adjusted voltages are used for the display
only. The adjusted voltages will not be sent over
the C AT Data Link to other modules. The customer
communication module is another module that m ay
receive information over the CAT Data L in k . The
adjusted voltages are not used in order to determine
the fault thresholds for the protective relaying
function. The GSC+P determines the values that are
not adjusted in both cases. The values that are not
adjusted for AC voltage are not shown in both cases.
The values that are not adjusted will be used instead
of the displayed values.
Procedure F or AC Offset
Adjustment
The adjusted voltages and the adjusted currents
are shown on the left side of the upper display. The
percentage of the offset is s hown on the right side of
the upper display. The user can adjust each voltage
and current up to ±5.0% in increments of 0.04%.
Note: Service Mode cannot be entered when the
Engine Contro l Switch (ECS) is in the AUTO position.
1. Startthe engine and run the engine at rated speed.
Enter service mode and enter the password.
“OP9” is showing on the lower display. Refer to
System Operation, “Password Entry OP3” for
more information.
2. Press the “SCROLL UP” key once. “OP 10” is
showing on the lower display.
3. Press “ SELECT” key. “AC CAL” is showing on the
lower display. The voltage in phase “A” is showing
on the left side of the upper display. The voltage in
phase “A” is line to neutral voltage.
4. Press “SELECT” key. The offset percentage value
is flashing on the right side of the upper display.
5. Press the “SCROLL UP” key or press the
“SCROLL DOWN” key in order to adjust the
voltage value to the desired value. The percentage
value continues flas hing.
6. Press “ENTER” key. The percentage value display
will stop flashing.
7. Press “SCROLL UP” key. Repeat steps 3, 4, 5 and
6 for the other setpoints.
8. Press the “EXIT” key. “OP 1” is showing on the
lower displa y.
9. Press the “EXIT” key. The display returns to the
normal mode.
i02898801
Parallel S etpoint Tuning OP-11
SMCS Code: 4490
OP11 is the option for programmin g some o f the
Synchronization setpoints. For more information,
refer to Systems Operation, “Synchronization Tuning
Procedure”. P305, P306, P307, P308, and P309 are
the setpoints that are affected by this procedure.
The setpoints are described in Systems Operation,
“Parallel P rogramming OP5-3”.
Procedure For Programming
Synchronization Setpoints
The generator set must be operating at rated speed
when the technician is performing this procedure.
The parallel functions are available in OP11 by using
the Parallel M ode Switch.
Note: If a parallel function is requested with the
Parallel Mode Switch, the OP11 display will be
replaced by the display of the synchroscope while
the synchronization is being p erformed. After
synchronization, the display will return to O P11.
1. Start the engine and run the engine at rated speed.
Enter Service Mode and enter the password. For
more information, refer to Systems Operation,
“Password Entry - OP3”. “OP9” should now be
showing on the lower display.
2. Press the “SCROLL UP” key twice. OP11 is
showing on the lower display.
3. Press the “SELECT”. “P305” is showing on the
lower displa y.
4. Press the “SCROLL UP” key or the “SCROLL
DOWN” key. The next setpoint and the value of
the setpoint is showing. Repeat this step until the
desired setpoint is showing.
5. Press the “SELECT” key. The value of this setpoint
is sho w ing.
6. Press the “SCROLL UP” key or the “SCROLL
DOWN” key in order to adjust the value of the
setpoint. In order to rapidly scroll through a large
range of values, press the appropriate “SCROLL”
key and hold the key.
7. Press the “ENTER key”. The value of the setpoint
stops flashing.
8. Repeat Steps 2, 3, 4, 5, 6, and 7 until all of the
desired setpoints are adjusted.
9. Press the “EXIT” key. OP1 is showing on the lower
display.