KENR8601 45
Systems Operation Section
Table 8
OP5-3 Setpoints - Paralleling Programming
Setpoint
Name Description
Range Of Value
Factory
Default
P301
Synchronization
Enable
Enables or disables the synchronization
function, and specifies the type of Load
Share control
being driven.
0 - disabled
1-Woodward
0
P302
Breaker Coil Time
Limit
The maximum amount of time the
breaker coil can be en ergized without
damaging the coil.
0.2 to 5.0 seconds in increments
of 0.1 second
1.0
second
P303 Voltage Limit Enable
Enables or disables the generator/bus
voltage checking during automatic
synchroniza
tion
0 - disabled
1 - enab led
1
P304 Voltage Limit
The maximum acceptable difference
between the bus voltage and the
oncoming voltage, expressed as a
percentage of bus voltage.
1% to 15 % in increments of 1% 1%
P305
(1)
Phase Tolerance Limit The maximum phase ang le m agnitude
allowed f or breaker closure
1to25degreesinincrementsof
1degree
5 degrees
P306
(1)
Dwell Time The time during which the phase angle
between the generator and the bus
during sync
hronization.
0.1 to 1.0 seconds in increments
of 0.1 second
0.5
second
P307
(1)(2)
Speed Control Gain Controls how fast the engine speed will
change during synchronization.
0.0% to 100.0% in increments of
0.1%
50.0%
P308
(1)(2)
Speed Contr
ol Rate
Controls th
e rate of change of the phase
angle differencebe tween the generato r
and the bus during synchronization.
0.0% to 100.
0% in increments of
0.1%
50.0%
P309
(1)(2)
Speed Control
Damping
Controls the amount of overshoot and
settling time of engine speed d uring
synchronization.
0.0% to 100.0% in increments of
0.1%
0.0%
P310
Dead Bus Cl
osure
Enable
Enables or disables automatic closing
toadeadbus.
1 - enabled
(3)
0 - disabled
0
P311 Dead Bus Limit
The m aximum acceptab le voltage for
the bus to be conside red dead, as a
percent of rated voltage.
5% to 50% in i ncreme nts of 1% 20%
P312
Dead Bus On Time
Delay
TheamountoftimetheGSC+Pwaits
before cl
osing to a dead bus.
0 to 120 second s in increments
of 1 second
0
seconds
P313 Frequency Match
Notification Time
The amount of time before n otification
of possible synchronization failure.
Must not be greater than the Maximum
Synchronization Time.
5 to 1000 seconds in increments
of 1 seconds
20
seconds
P314 Maximum
Synchronization Time
The maximum amount of time to spend
attempt
ing to synchronize before
setting the Synchronization Time-out
Alarm
5 to 1000 seconds in increments
of 1 second
30
seconds
(1)
P305, P306, P307, P308, and P309 can be adjusted to precisely match individual engine response and breaker closure characteristics
using OP11 - Synchronization Setpoint Tuning.
(2)
The GSC+
P uses P-I-D (proportional-integral-derivative) control to accomplish synchronization qu ickly an d smoothly. The P parameter, I
parame
ter, and D parameter a re independantly controlled by setpoints P307, P308, and P309 respectively. Adjusting any one of these
setpoi
nts will not affect the other two settings. For more information, see Systems Operation, “Synchronization Mode” Setpoint Tuning.
(3)
Dead bus closure will only work in the automatic mode, NOT in permissive mode or semi automatic mode.