KENR8601 49
Systems Operation Section
5. Press the “SELECT” key. The value of the setpoint
is fl ashing.
6. Press the “SCROLL UP” key or the “SCROLL
DOWN” key in order to adjust the value of the
setpoint.
7. Press the “ENTER” key. The value of the setpoint
stops flashing. Repeat steps 4, 5, 6, and 7 until all
the desired setpoints are a djusted.
8. Press the “EXIT” key. “OP 1” is showing on the
lower displa y.
9. Press the “EXIT” key. The display returns to
Normal M o de .
Table 9
OP6-0 Setpoi
nts
(1)
- Spare Input/Output Programming
Setpoint
Name Description
Range Of Value Factory Default
SP01 Spare Input 1 Active
State
Input state used by the
GSC+P to declare that
a SP01 fault exists.
0-activelow
1 - active high
0
SP02 Spare input 1
Response
GSC+P response to a
SP01 fault.
0 - shutdown
1 - alarm
0
SP03 Spare Input 1 Time
Delay
Amount of time th e
GSC+P waits before
responding to a SP1
fault.
0 to 250 seco nds in
increments of 1
0 secon ds
SP04 Spare Input 2 Active
State
Input state used by the
GSC+P to declare that
a SP02 fault exists.
0-activelow
1 - active high
0
SP05 Spare Input 2
Response
GSC+P response to a
SP02 fault
0 - shutdown
1 - alarm
0
SP06 Spare Input 2 Time
Delay
Amount of time th e
GSC+P waits before
responding to a SP02
fault.
0 to 250 seco nds in
increments of 1
0
SP07 Spare Input 3 Active
State
Input state used by the
GSC+P to declare that
a SP03 fault exists.
0-activelow
1 - active high
0
SP08 Spare Input 3
Response
GSC+P response to a
SP03 faul
t.
0 - shutdown
1 - alarm
0
SP09 Spare Input 3 Time
Delay
Amount of time th e
GSC+P waits before
responding to a SP03
fault.
0 to 250 seco nds in
increments of 1
0 secon ds
SP10 Spare Input 4 Active
State
Input state used by the
GSC+P to declare that
a SP04 fault e xist.
0-activelow
1 - active high
0
SP11 Spare Input 4
Respon
se
GSC+P response to a
SP04 fa
ult.
0 - shutdown
1 - alarm
0
SP12 Spare Input 4 Time
Delay
Amount of time th e
GSC+P waits before
responding to a SP04
fault.
0 to 250 seco nds in
increments of 1
0 secon ds
(continued)