186 KENR8601
Testing and Adjusting Section
(Table 26, contd)
Service Table - R
ecord Of Setpoint Values
Generator Description : Site, Serial No., EMCP II+ Part Number., etc..
Engine /Generator Programmin g OP5-0
Setpoint Specified Value
Actual Value
(1)
Setpoint Description
Possible Values
Default Value
P024
Crank Time Delay
0 to 20 seconds 5 seconds
P025
Oil Tem perature Sensor
Installed
0=w/osensor,
1 = w/sensor
0
P026
High Oil Te m perature
Shutdown
85 to 123°C
(185 to 253°F)
107°C (225°F)
P027
Shutdown Override For
High Oil Tempe
rature
0 = alarm,
1 = shutdown
0
P028 Nameplate Voltage 100 to 25kV 480V
P029
Nameplate Current
0 to 4000A 600A
P030 Nameplate Po wer 0 to 10MW 400kW
P031 Rated Frequency 50, 60 or 400 Hz 60
P032
Connection Configuration
Of Generator
0 = wye, 1 = delta 0
P033
Number Of Generator Poles
0to254 4
(1)
The actual value s pace is provided for recording and comparing valu e s during future servicing or troubleshooting of the particular
generator set.
Note: This table provides a record of setpoint values
for a singular generator set. The table is intended
to be an easy reference for future servicing or
troubleshooting of a particular generator set.
Table 27
Service Table - Record Of Setpoint Values
Generator Description : Site, Serial No., EMCP II+ Part Number., etc..
Engine /Generator Programmin g OP5-0
Setpoint Specified
Value
Actual Value
(1)
Setpoint D
escription
Possible Values
Default Va
lue
P001
Fuel Solenoid Type 0 = ETR, 1 = ETS
0
P002
Units Show
n
0=Eng,1=metric 0
P003
Shutdown Override For
Engine Fault
0 = shutdown,
1 = alarm
0
P004
Shutdown E
nable For
Sensor Fault
0=alarm,
1 = shutdown
0
P005
Coolant Loss Sensor
Installed
0=w/osensor,
1=w/sensor
0
P006
Shutdown Override For
Coolant Loss Fault
0 = shutdown,
1 = alarm
0
P007
System Voltage
24 volts o
r32volts
24
P008
This Setpoint Is Not Used.
NA NA
(continu
ed)