KENR8601 75
Troubleshooting Section
•
NO – The GSC+P does NOT show a diagnostic
code on the u pper dis play. Procee d to Test Ste p 2.
Te st Step 2. CHECK THE YELL OW FAULT
ALARM INDICATOR
A. Check the display of the GSC+P for the yellow
fault alarm indicator.
Expected Result:
The yellow fault alarm indica to r is ON
CONTINUOUSLY.
Results:
•
YES – The y ellow f au lt alarm indicator is
ON CONTINUOUSLY. The GSC+P has been
programmed to override the normal shutdown
response. The setpoints have been modified and
the GSC+P treats the condition as an alarm fault.
The engine will continue to ru n.
Repair: In order to view the setpoints, refer
to Systems Operation, “Engine/Generator
Setpoint Viewing O P2-0”. In order to reprogram
the setpoints, refer to Systems Operation,
“Engine/Generator Programming OP5-0”.
STOP.
•
NO – The yellow fault alarm indicator is not
illuminated at all. Proceed to Tes t Step 3.
Te st Step 3. CHECK FOR THE RED FAULT
SHUTDOWN INDICATOR
A. Che ck the display area of the GSC+P for th e red
fault shutdown indicator.
Expected Result:
The red fault shutdown should be FLASHING.
Results:
•
YES – The red fault shutdown indicator is
FLASHING and the engine remains running.
Proceed to Test Step 4.
•
NO – All fault indicators are OFF. A problem that
is occurring should cause the GSC+P to shut
down the engine. It is possible to program the
GSC+P setpoints to a value that does not allow
the situation to be recognized by the GSC+P as a
shutdown condition.
Repair: Check the appropriate setpoints for
correct values. In order to view the setpoints,
refer to System Operation, “Engine/Gen erat or
Setpoint Viewing OP2-0”. In order to reprogram
the setpoints, refer to System Operation,
“Engine/Generator Programming OP5-0”.
STOP.
Test Step 4. CHECK K1 INDICATOR ON
GSC+P DISPLAY
A. The red fault shutdown indicator is FLASHING
and the engine remains running.
B. Check the upper display of the GSC+P.
Expected Result:
The K1 symbol is showing on the GSC+P upper
display.
Results:
•
YES – The K1 symbol is showing on the GSC+P
upper display. The red fault shutdown indicator is
FLASHING and the engine remains running. The
GSC+P may have failed.
Repair: The GSC+P may have failed. It is u nlike ly
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer to Testing and
Adjusting, “EMCP Electronic Control (Generator
Set)-Replace”
STOP.
•
NO – The K1 symbol is n o t showing at all on the
GSC+P upper display. Proceed to Test Step 5.
Test Step 5. CHECK THE GSC+P RELAY
MODULE.
The engine remains running and the red fault
shutdown indicator is FL ASHING.
A. In the generator housing, remove BOTH of the
wires from RM-13 on the GSC+P.
Expected Result:
The engine should shut down.
Results:
•
OK – The engine shuts down.