148 KENR8601
Troubleshooting Section
Te st Step 3. CHECK THE F UNCTION OF
THE BUS RELAY.
A. Carefully reconnect any power wires of the DBR
that may have previously been removed.
B. Ens ure that the bus is live.
C. Use a cable probe to measure the voltage at pin
29 of the GSC+P.
Expected Result:
The voltage should measure 10.5 ± 1.0 DCV.
Results:
•
OK – The voltage is 10.5 ± 1.0 DCV.
Repair: The GSC+P is functioning p roperly. The
problem is in the wiring or the component that is
connected to the input of the dead bus sensor of
theGSC+P.UsetheFMIinformationandtheDead
Bus Sensor input System Schematic to find the
exact cause of the diagnostic code.
STOP.
•
NOT OK – T he voltage is incorrect.
Repair: The GSC+P has faile d. Replace t he
GSC+P. Refer to Tes tin g and Ad jus tin g, “EM PC
Electronic Control (Generator Set) - Replace”.
STOP.
i02891044
GSC CID 1168 - FMI 04
SMCS Code: 445B-035
Conditions Which Generate This Code:
This dead bus sensor provides an additional
indication of the state of the bus. The bus can be
live or dead. The input of the dead bus sensor is
compared to the reading of the bus voltage, and the
diagnostics are produced if the measurements differ.
When the input of the dead bus sensor is inactive, the
input w ill float to approximately 10.5 DCV. An inactive
state indicates that the bus is live. When the input of
the dead bus sensor is active, the bus will be dead.
The possible cause of a CID 1168 FMI 04 is a short
from the input signal of the dead bus sensor to
negative battery terminal (“BATT-”).
A CID 1168 FMI 04 is detected under the following
condition.
•
The voltage of the Phase A of the bus is greater
than 50% of the rated voltage and the input of the
dead bus sensor is fl oating. The voltage of the
Phase A is determined by the “BTB+” input to the
GSC+P.
The GSC+P treats a CID 1168 FMI 04 as an alarm
fault. The dead bus paralleling func tio n w ill be
stopped when this diagnostic code is detected. No
other synchronization processes w ill be affected.
Test Step 1. CHECK TH E INACTIVE
VOLTAGE LEVEL OF THE INPUT OF THE
DEAD BUS SENSOR .
A. Turn the E ngine Control Switch (ECS) to STOP.
B. Locate the wire that is connecting pin 29 of
the GSC+ P to terminal “DBR-9” of the Dead
Bus Relay (D BR). Remove this wire at terminal
“DBR-9” of the DBR only. Pin 29 of G SC+P will
remain connected to the wire.
C. Use a cable probe to measure the voltage at pin
29 of the GSC+P.
Expected Result:
The voltage should measure 10.5 ± 1.0 DCV.
Results:
•
OK – The voltage level is 10.5± 1.0 DCV. Proceed
to Test Step 2.
•
NOT OK – The voltage level is not within the
correct range.
Repair: The GSC+P may have failed. It is u nlike ly
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer to Testing And
Adjusting, “EMCP Electronic Control (Generator
Set)-Replace”.
STOP.
Test Step 2. CHECK THE FUNCTION OF
THE BUS RELAY.
A. Reconnect the wire that is connecting pin 29 of
the GSC+P to terminal “DBR-9” of the DBR.
B. Use a cable probe to monitor the voltage on pin
29 of the GSC+P.
C. Ensure that the bus is dead, or carefully
disconnec t po we r f ro m the re lay coil of the DBR.