52 KENR8601
Systems Operation Section
1. Turn the ECS to the STOP position in order to
shut down the engine. Enter service mode and
enter the password. OP 4 is showing on the lower
display. For more information, refer to Systems
Operation, “Service Mode”for more information.
Refer to the Systems Operation, “Password Entry
OP3”for more information.
2. Press the “SCROLL UP” key five times. “OP 8” is
showing on the lower display.
3. Press the “SELECT” key. “AC01” is showing. The
value of the setpoint is also showing. The value
will be between 0 to 255.
4. Press the “SELECT” key. The value of the setpoint
is fl ashing.
5. Press the “SCROLL UP” or the “SCROLL DOWN”
key in order to adjust the value of the A C01
setpoint. Match the value that is shown on the
ATB+ with the line voltage (A) to the line voltage
(B).
6. Press the “ENTER” key. The value of the setpoint
stops flashing.
7. Press the “SCROLL UP” key. Repeat steps 3, 4, 5
and 6 for setpoints AC02 through AC06.
8. Press the “EXIT” key. “OP 1” is showing on the
lower displa y.
9. Press the “EXIT” key. The display will return to the
Normal M o de .
i02898763
Engine Setpoint Verification
OP9
SMCS Code: 4490
OP9 is the option for verifyin g that the EMCP II+
operates correctly when a fault occurs with low
oil pressu re , high co olant temperat ure or eng ine
overspeed. An overspeed fault for the engine causes
the GSC+P to shut off the engine. When a low oil
pressure fault or a high water temperature fault
is detected the GSC+P will shut off the engine or
the GSC+P will sound th e alarm ac cording to the
programmed setpoint P0 03. Setpoint P003 is the
shutdown override setpo int fo r an engine fault.
OP9 is only for verification of certain engine setpoints.
OP5-0 is used for the actual programming of these
setpoints. The setpoints that are verified by this
procedure are listed below.
P003 Shutdown Override For Engine Fault –
P003 is the GSC+P response to a low engine oil
pressure. P003 is also the response to a high coolant
temperature fault. 0 is for engine shutdown. If P003
is set to 1 then the alarm responds only. The GSC+P
will override engine shutdown. The default value for
P003 is 0.
P010 Engine Overspeed – The GSC+P uses
setpoint P010 in order to show an overspeed fault for
the engine. The engine overspeed setpoint is 1.18
times the rated speed for all 60 Hz applications. The
values vary from 500 to 4330 rpm. The values are
changed in increments of 10. The default value for
P010 is 2120.
P013 Low Oil Pressure Shutdown At Rated
Speed – The oil pressu re is us ed by the GSC+P to
declare that a low oil pressure shutdown fault exists
with the engine at rated speed. The speed must
have exceeded the oil step speed setting for at least
nine seconds. The values vary from 34 to 420 kPa
(5 to 61 psi). The increments increase with a value of
1. The default value for P013 is 205 kPa (30 psi).
Note: When the oil pressure drops to a level that
is within 34 kPa (5 psi) of the P013 setpoint, a low
oil pressure alarm is issued by the GSC+P and the
optional ala rm module.
P015 High Water Temperature Shutdown – The
coolant temperature is used by the GSC+P to declare
that a high coolant temperature shutdown fault
exists after a 10 second delay. The values vary from
85 to 123°C (185 to 253°F). The increments increase
with a value of 1. The default value for setpoint P015
is 107°C (225°F).
Note: A high water coolant temperature alarm is
issued by the GSC+P when the coolant temperature
rises to a level that is within 6°C (11°F) of the P015
setpoint.
The following conditions are required before the
engine setpoints are verified.
•
Thepreviouslylistedsetpoints must be correct
for the engine application. Refer to System
Operation, “Service Mode” in order to view a
list of the setpoints . Re fer to System Operation,
“Setpoint Programming OP5” in order to program
the setpoints.
•
The engine is checked at idle and rated speed. No
faults should be present at the initial starting. If
necessary, troubleshoot and correct any fault.