Troubleshooting Section
“COOLDOWN/STOP” – The engine maintains rated
speed for the cooldown period. The cooldown period
is programmable from 0 to 30 minutes. After the
cooldown period elapses, the engine is shut down.
The GSC+P shows diagnostic codes on the upper
display and on the fault indicators as the diagnostic
code occurs. The GSC+P is ON with the ECS in this
position.
Note: The remote start/stop contact is connected to
the GSC+P start input via a terminal strip. Before
troubleshooting, disconne c t the remote start/stop
initiate contac ts from the termin al strip.
Note: Diagnostic codes are created when the
harness connector is disconnected from the GSC+P
during these troubleshooting procedures. Clear these
created diagnostic codes after the particular problem
is correcte d and the particular d iagnostic code is
cleared.
The possible causes of a CID 0336 FMI 02 are listed
below.
•
None of the GSC+P inputs from the ECS are
connected to ground.
•
More than one of the GSC+P inputs from the ECS
is connected to “BATT-”at the same time. The
one exception is the start input. The start input
of the GSC+P is also connected to the remote
start/stop initiate contact. The contact is controlled
by the customer. The GSC+P will then accept a
connection from the battery negative at the start
input. Other inputs from the ECS are also received.
The CID 0336 FMI 02 is the only ECS diagnostic code
that is detected by the GSC+P. Clear the diagnostic
code from the fault log after troubleshooting is
complete. The G S C+P treats a CID 0336 FMI 02 as
a shutdown fault. Use these procedures for an active
diagnostic code or an inactive diagnostic code.
Te st Step 1. CHECK FOR AN OPEN
CIRCUIT IN THE “OFF /RESET” POSITION
A. If equipped, disconnect the remote start/stop
initiate contac ts from the termin al strip in the
customers’ connection box.
B. Disconnect the harness connector from the
GSC+P.
C. Check whether the corresponding contact of the
GSC+P harness connector is the only contact that
is connected to “BATT-”.
D. At the GSC+P harness connector, measure the
resistance from pin “39” to “BATT-” of the relay
module. Mea sure the resista nce fro m pin s “32”,
“33” and “40” to the “BATT-” terminal. Make a note
of the resistanc es that are measured.
Expected Result:
The resistance that is measured from pin “39” to
the “BATT-” terminal of the relay module should be
5 ohms or less. The resistance that is measured
from pins “32”, “33” and “40” to the “BATT-” terminal
should be greater than 5000 ohms.
Results:
•
OK –Allresistancemeasure ments are correct.
Proceed to Test Step 2.
•
NOT OK – The resistance measurements are
NOT correct. T he harness wiring with the inco rrect
resistance measurement is open or the harness
wiring has failed.
Repair: Repair the harness wiring or replace the
harness wiring. Repair the wiring or replace the
wiring between “BATT-”, the ECS, and the GSC+P
connector. Reconnect the remote start/stop initiate
contacts after troubleshooting is complete.
STOP.
Tes t Step 2. CHECK FOR AN OPEN
CIRCUIT IN THE “AUTO” POSITION
A. If equipped, the remote s tart/stop initiate contacts
will rema in disconnected from the term inal strip in
the customers’ connection box.
B. The harness connector remains disconnected
from the G SC+P.
C. Check whether the corresponding contact of the
GSC+P harness connector is the only c ontact that
is connected to “BATT-”.
D. Place the ECS in the AUTO position. Measure the
resistance from p in “40” of the GSC+P harness
connector to the “BATT-” terminal of the relay
module. Mea sure the resista nce fro m pin s “32”,
“33” and “39” to the “BATT-” terminal. Make a note
of the resistanc es that are measured.
Expected Result:
The resis tance that is measured from pin “40” to the
“B−” terminal of the relay module should be 5 ohms
or less. The resistance that is m easured from pins
“32”, “33” and “39” to the “B−” terminal should be