80 KENR8601
Troubleshooting Section
Results:
•
OK – The wires in the harness for the GSC+P
measure less than 5 Ohms.
Repair: The ATB+ has failed. Rep lace the ATB+.
Refer to the Testing and Adjusting Sectio n,
“EMPC Electronic Control (AC Transformer Box)
-Replace”.
STOP.
•
NOT OK – The wires in the harness for the GSC+P
do NOT m easure less than 5 Ohms.
Repair: Repa ir the wiring or replace the harness
for the GSC+P. Verify that the repairs fixed the
problem.
STOP.
Te st Step 10. CHECK THE INPUTS OF
THE ATB+
A. The wires that were previously disconnected from
terminals 51, 52, and 53 will remain disconnected.
The only wires which are connected to these
terminals should lead into the ATB+.
B. At the terminal strip of the ATB+, measure the
resistance between the following terminals:
terminal 51 to terminal 50, terminal 52 to terminal
50, and terminal 53 to te rminal 50.
Expected Result:
All the resistance measurements s hould read less
than1Ohm.
Results:
•
OK – All the resistance measurements do read
less than 1 Ohm.
Repair: The GSC+P may have failed. It is unlikely
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer to Testing And
Adjusting, “EMCP Electronic Control (Generator
Set) - Replace”.
STOP.
•
NOT OK – One or more of the resistance
measurements are NOT correct.
Repair: The ATB+ has failed. Replac e the AT B+.
Refer to the Testing and Adjusting Section,
“EMPC Electronic Control (AC Transformer Box)
-Replace”.
STOP.