KENR8601 191
Testing and Adjusting Section
(Table 28, contd)
Service Table - R
ecord Of Setpoint Values
Generator Description : Site, Serial No., EMCP II+ Part No., etc..
OP5-1 Setpoints
(1)
- Protective Relaying Pro g ramming
Setpoint Specified Value
Actual Value
(1)
Name
Range Of Value
Factory
Default
P141 KW Level Relay
Disengage Thre
shold
0 to 110% of nameplate power in
increments of 1%
100%
P142 KW Level Relay
Disengage Time Delay
0 to 120 seconds
(2)
in increments
of 1
10
seconds
(1)
The setpoints are programmed at the factory to the default value. The setpoints may be changed in order to satisfy customer or application
requirements.
(1)
The actual value s pace is provided for recording and comparing valu e s during future servicing or troubleshooting of the particular
generator set.
(2)
When programmed to 0 seconds, the actual time is from 0.5 to 1.0 seconds.
Note: This table provides a record of setpoint values
for a singular generator set. The table is intended
to be an easy reference for future servicing or
troubleshooting of a particular generator set.