132 KENR8601
Troubleshooting Section
•
NOT OK – Either one of the resistance
measurements are NOT correct. The relay module
has failed.
Repair: Replace the relay module. Refer to Testin g
And Adjusting, “Relay Module - Replace”.
STOP.
i02890370
GSC CID 0447 - FMI 12
SMCS Code: 4490-035-R7
Conditions Which Generate This Code:
The Fuel Control Rela y (FCR) is n ot used on the
C32 EMCP II+P system. The FCR is located within
the relay module. The fuel control solenoid is located
in the fuel system of the engine. The Electronic
Governor (EG) is located on the subpanel.
Note: Whenever the GSC+P activates the FCR or
attempts to activate the FCR, “K7” is shown on the
lower display. When the FCR is not activated, “K7” is
not shown. Also, setpoint P001 selects the type of
the fuel control solenoid. 0 = ETR. 1 = ETS.
The possible cause of a CID 0447 FMI 12 is an open
coil or a shorted coil of the FCR.
The system responses to these diagnostic codes are
listed b elow.
•
If a CID 0447 FMI 12 occurs and the engine is
running, a CID 056 6 F MI 0 7 will become active.
A CID 0566 FMI 07 describes an unexpected
shutdown. The shutdown mode is functioning. The
engine stops.
•
If a CID 0447 FMI 12 occurs and the engine is
NOT running, then the engine can not start and
the engin e can not run.
The GSC+P treats a CID 0447 FMI 12 as an alarm
fault. Active alarm faults are shown on the display
when the “Alarm Codes” key is pressed. Also, the
ECS must be in any position except the OFF/RESET
position. Clear the diagnostic code from the fault log
after troubleshooting is complete.
Note: This troubleshooting procedure is for an active
CID 0447 FMI 12 or the troubleshooting procedure is
for an inactive CID 0447 FMI 12.
Test Step 1. CHECK THE STATUS OF THE
DIAGNOSTIC CODE.
A. Turn the Engine Con trol Switch (ECS) to the
OFF/RESET position and then turn the ECS to
the STOP position.
B. Press the “Alarm Codes” key.
C. Observe the upper display. Check that the CID
0447 FMI 12 is active.
D. If the diagnostic code is not active, enter the
Service Mode. View the fault log for a OP1. Check
that the diagnostic code is inactive.
Expected Result:
A CID 0447 FMI 1 2 is displayed as an active
diagnostic code or CID 0447 FMI 12 is displayed as
an inactive diagnostic code.
Results:
•
OK – The CID 0447 FMI 12 is active or the CID
0447 FMI 12 is inactive. Proceed to Test Step 2.
•
NOT OK – The CID 0447 FMI 12 has not occurred.
The diagnostic code is not active and the diagnostic
code is not inactive. STOP.
Tes t Step 2. CHECK THE INTERNAL
CABLE OF THE RELAY MODULE.
Note: Only open the relay module in a dry
environment. If the inspection and repair takes
more th an approxi mately twenty minutes replace
the desiccant bag in the GSC+P housing. Refer to
Testing And Adjusting, “Relay Module - Replace”.
A. Turn the ECS to the OFF/RESET position.
B. Disconnect the battery negative cable.
C. Temporarily, remove the relay module from the
GSC+P. Refer to Testing And Adjusting, “Relay
Module - Replace”.
D. Check the cable that attaches the relay module
to the GSC+P.
Expected Result:
The cable should be firmly seated in the connector.
The clamp should be in place. The cable should not
be damaged.