KENR8601 115
Troubleshooting Section
i02888018
GSC CID 0333 - FMI 04
SMCS Code: 4490-035
Conditions Which Generate This Code:
g01438113
Illustration 69
System Schematic For Alarm Module (ALM)
The Alarm Module (ALM) is available as an option.
The ALM may be mounted on the front panel. Also,
theALMmaybeplacedatadistancefromthecontrol
panel as a remote annunciator. The ALM is used in
order to satisfy the requirements of the customer.
TheALMmaybeusedinordertosatisfyNational
Fire Protection Association (NFPA) requirements by
annunciating the presence of a diagnostic code.
The ALM communicates with the GSC+P by a serial
data link. When the data link malfunctions, all of the
indicators on the ALM, that are controlled by the data
link, flash at a rate of .5 Hz.
Note: The maximum number of the ALM or the
Customer Interface M odule (CIM) that may be
connected to the serial data link is equal to three.
The maximum distance between a module and the
GSC+P is 305 m (1000 ft). If these specifications are
not met, the ALM indicators may begin to flash. Also,
the GSC+P may show a CID 0333 FMI 04. If the
setup is not in co mpliance with the specifications,
reduce the number of modules and/or shorten the
distance to the modules.
Note: Diagnostic codes are created when the
harness connector is disconnected from the GSC+P
during these troubleshooting procedures. Clear these
created diagnostic codes after the particular problem
is corrected and the particular diagnostic code is
cleared.
The possible cause of a CID 0333 FMI 04 is a short
from the negative battery terminal “(BATT-)” to the
data signal.
TheGSC+PtreatsaCID0333FMI04asanalarm
fault. Clear the diagnostic code from the fault log
after troubleshooting is complete.
Note: If a CID 0333 FMI 04 is active on the upper
display and no alarm module is installed, then check
the terminal strips on the subpanel for a short.
Perform the check from the signal wire to “BATT-”.
Also, check the customers’ connection box for a short
from the alarm data signal wire to “BATT-”.