134 KENR8601
Troubleshooting Section
•
If a CID 0448 FMI 12 occurs and the PSR is
inactive, any customer’s equipment that is wired to
RM-25 will remain deactivated and any customer ’s
equipment tha t is wired to RM-26 will remain
activated.
The GSC+P treats a CID 0448 FMI 12 as an alarm
fault. Active alarm faults are shown on the display
when the “Alarm Codes” key is pressed and the
Engine Control Switch (ECS) is in any position except
the O FF/RESET position. Clear the diagnostic code
from the fault log after tro u bleshooting is complete.
This troubleshooting procedure is for an active CID
0448 or the troubleshooting procedure is for an
inactive CID 448 FMI 12.
Te st Step 1. CHECK T HE STATUS OF THE
DIAGNOSTIC CODE.
A. Turn the EC S to the OFF/RESET position and
then turn the ECS to the STOP position.
B. Press the “Alarm Codes” key.
C. Ob serve the upper display. Check that the CID
0448 FMI 12 is active.
D. If the diagnostic code is not active, enter the
Service Mode. View the fault log for a OP1. Check
that th e diagnostic code is in active.
Expected Result:
A CID 0448 FMI 12 is dis pla yed as an a ctive
diagnostic code or CID 0448 FMI 12 is displayed as
an inactive diagnostic code.
Results:
•
OK – The CID 0448 FMI 12 is active or the CID
0448 FMI 12 is inactive. Proceed to Test Step 2.
•
NOT OK – The CID 044 8 FMI 12 has not occurred.
The diagnostic c ode is not active and the diagnostic
code is not inactive. STOP.
Te st Step 2. CHECK THE INTERNAL
CABLE OF THE RELAY MODULE.
Note: Only open the relay module in a dry
environment. If the inspection and repair takes
more than approximately twenty minutes replace
the desiccant bag in the GSC+P housing. Refer to
Testing And Adjusting, “Relay M o dule - R eplace”.
A. Turn the ECS to the OFF/RESET position.
B. Disconnect the negative battery cable.
C. Temporarily, remove the relay module from the
GSC+P. Refer to Testing And Adjusting, “Relay
Module - Replace”.
D. Check the cable that attaches the relay module
to the GSC+P.
Expected Result:
The cable should be firmly seated in the connector.
The clamp should be in place. The cable should not
be damaged.
Results:
•
OK – The cable is firmly seated in the connector.
The clamp is in place. The cable is not damaged.
Reassemble the relay module to the GSC+P.
Proceed to Test Step 3.
•
NOT OK – One or more of the components are
damaged or the components are missing.
Repair: Replace the clamp if the clamp is missing.
If the cable is damaged, replace the GSC+P. Refer
to Testing and Adjusting, “EMCP Electronic Control
(Generator Set) - Replace”.
STOP.
Tes t Step 3. FUNCTIONAL CHECK OF
THE PSR
A. Turn the ECS to the OFF/RESET position.
B. Reconnect the negative battery cable.
C. Disconnect all wires from RM-25 of the relay
module.
D. Remove fuse “F9” from the relay module.
E. At the relay module, measure the resistance from
RM-25toRM-11.Makeanoteoftheresistance
measurement.
F. Turn the ECS to the START position. Measure the
resistance from RM-25 to RM-11. Make a note of
the resistance measurement.
Expected Result:
The initial resistance measurement after removing
the wires and the fuse from the relay module
should be greater than 5000 ohms. The resistance
measurement should be less than 5 ohms when the
ECS is placed in the START position.