KENR8601 53
Systems Operation Section
Procedure For Overspeed
Verification
Note: Service mode canno t be accessed when the
Engine Contro l Switch (ECS) is in the AUTO position.
1. Start and run the engine at rated speed. Enter
service mode and enter the password. “OP 9” is
showing on the lower display. Refer to System
Operation, “Password Entry OP3”.
2. Press the “SELECT” key. The value of the
overspeed setpoint “P010” is showing on the
upper display. The default value for P010 is 2120.
“SC1” is showing on the lower display. “SC1” is
followed with the present engine speed value.
3. Press “SE LECT” key. The se tpoint value is
flashing on the upper display.
4. Decrease the setpoint value by pressing the
“SCROLL D OWN” ke y. Th e default setpoin t value
is 2120. The d efau lt va lu e is flashing on the upper
display. The setpoint value decreases by 10 rpm
with each press of the scroll down key. Press the
“SCROLL D OWN” key unt il t he setpoint va lue
is past the present engine speed v alue that is
showing on the display.
When the setpo i nt value is less than the present
engine speed value, the engine will shut down. The
engine oversp eed in dicator will flash. The GSC+P
will no longer be in the service mode.
Procedure For Oil Pressure
Verification
Note: Service mode cannot be entered when the
ECS is in the AUTO position.
1. Start the engine and run the engine at rated speed.
Enter service mode and enter the password.
“OP 9” is showing on the lower display. Refer to
System Operation, “Password Entry OP3” for
more information about entering the password.
2. Press “SELECT” key. The value of the overspeed
setpoint P010 is showing on the upper display.
The default value for P010 is 2120. “SC1” is
showing on the lower display. The present engine
speed value is then shown on the display.
3. Press the “SCROLL UP” key once. The value of
the P013 setpoint for low oil pressure shutdown
at rated speed is showing on the upper display.
205 kPa (30 psi) is the default value. The present
oil pressure value is shown on the display.
4. Press “SE LECT” key. The se tpoint value is
flashing on the upper display.
5. The setpoint value that is flashing on the upper
display is increased by pressing the “SCROLL
UP” key. With each press of the “SCROLL UP”
key, the setpoint value in cre ases by five. Press
the “SCROLL UP” key until the setpoint value
is past the present value that is showing on the
lower displa y.
When the setpoint value is greater than the present
oil pressure value, the engine shuts down. The
indicator f or low oil pres sure should be flashing. The
GSC+P should not be in service mode.
Procedure For Verification of High
Water Temperature
Note: Service mode cannot be entered when the
ECS is in the AUTO position.
1. Start the engine and run the engine at rated speed.
Enter service mode and enter the password.
“OP 9” is showing on the lower display. Refer to
System Operation, “Password Entry OP3”.
2. Press “SELECT” key. The value of overspeed
setpoint “P010” is showing on the upper display.
The default value o f the overspeed setpoint is
2120. “SC1” is showing on the lower display. “SC1”
is followed with the present engine speed value.
3. Press the “SCROLL UP” k ey two times. The value
of the P015 setpoint for high water temperature
shutdown is showing on the upper display. The
default value for setpoint P015 is 107°C (225°F).
“P015” is showing on the upper display. “SC3” is
then shown o n t he lower display w hich is follo we d
by the present coolant temperature value.
4. Press the “SELECT” key. The setpoint value is
flashing on the upper display.
5. The setpoint value that is flashing on the upper
display is decreased by pressing the “SCROLL
DOWN” key. W ith each press of the “SCROLL
DOWN” key, the setpoint value decreases by five
degrees. Continue pressing the “SCROLL DOWN”
key until the setpoint value decreases past the
present coolant temperature value that is showing
on the lower display.
The engin e shuts down and the hig h water
temperature indicator begins flashing when the
setpoint value is less than the present coolant
temperature value. The GSC+P is no longer in
service m ode.