38 KENR8601
Systems Operation Section
Table 6
OP5-0 Setpoints - Engine/Generator Pro gramming
(1)
Setpoint
Name Description
Range Of Value Controller Default
P001
Fuel Solenoid
Type
Type of fuel sys
temsolenoidusedonthe
generator set. All Larne-built generators
covered by this mau al are ALWAYS
programmed a s
ETR(0),evenifthe
generator has an ETS fuel solenoid.
0-ETRfuelsole
noid
1 - ETS fuel solenoid
0
P002
Units Shown Type of measurement units shown on the
GSC+P display.
0-Englishunits(psi,
degrees F)
1 - Metric units (kPa,
degrees C)
0
P003
Shutdown
Override For
Engine Fault
GSC+P respond
s to a low engine oil
pressure or high coolant temperature faul t.
(Determined by application or customer.)
0 - engine shutdown
1 - alarm on ly
(shutdown override,
no engine shutdown)
0
P004
Shutdown
Enable For
Sensor Fault
GSC+P responds to a diagn ostic fault with
the engine oil pressure sensor, coolant
temperature
sensor, oil temperature sensor,
sensor power supply or coolan t loss sensor.
(Determined by application or customer.)
0 - alarm on ly
(shutdown override,
no engine shutdown)
1 - for engine shutdown
0
P005
Coolant Loss
Sensor Installed
Tel l s whe t he
r or not the optional engine
coolant loss sensor is installed on the
generator set.
0 - generato
rsets
without sensor
1 - generator sets with
sensor
0
P006
Shutdown
Override For
Coolant Loss
Fault
GSC+P responds to an engine coolant
loss fault. (Determined by application or
customer.)
0 - engine shutdown
1 - alarm on ly
(shutdown o
verride,
no engine shutdown.)
0
P007
System Voltage
24 Or 32 Vol
ts
System voltage (b attery voltage) of the
generator
set. (Determined by application or
customer.)
24 or 32 24
P008
N/A
This setpoint is not currently being used by
the GSC+P a
nd cannot be programmed.
N/A N/A
P009
Number Of Ring
Gear Teeth
Number of teeth on the rin g gear e ngine.
Used b y the GSC+P to dete rmine engine
speed.
95 to 350 teeth
in increments of 1
136 teeth for
MUI and PEEC
engines. 183 teeth
for EUI engines.
P010 Engine
Overspeed
Engine speed used by the GSC+P to declare
that an en
gine overspeed fault exists. The
engine overspeed setpoint (for all 60 Hz
applications) is 1.18 times the rated speed.
500to4330rpm
in increments of 10
2120 rpm
P011
Crank Te r mina te
Speed
Engine speed used by the GSC+P to
disengage the starting motor during engine
cranking.
100to100
0rpm
in increments of 10
400 rpm
P012
(2)
Oil Step
Speed
Engine s
peed used by the GSC+P for
distinguishing between rated speed and idle
speed when a low o il pressure fault exists.
400to1800rpm
in increments of 10
1350 rpm
P013
(3)
Low Oil Pressure
Shutdown At
Rated Speed
Oil pressure used by the GSC+P to declare
that a low oil pressure shutdown fault exists
with engine at rated speed (the engine must
have exceeded the oil step speed for at least
nine seconds).
34 to 420
kPa
(5 to 61 psi)
in increments of 1
205kPa(30psi)
(continued)