KENR8601 127
Troubleshooting Section
Repair: Replace the clamp if the clamp is missing.
If the cable is damaged, replace the GSC+P. Refer
to Testing and Ad ju stin g , “EMCP Electronic Control
(Generator Set) - Replace”.
STOP.
Te st Step 3. PERFORM A FUNCTIONAL
CHECK O N THE GFR.
A. Turn the ECS to the OFF/RESET position.
B. Reconnect the negative battery cable.
C. Disconnect all wires from RM-22 of the relay
module.
D. Rem o ve fuse “F5” from the r elay module.
E. At the relay module, measure the resistance from
RM-22toRM-7.Makeanoteoftheresistance
measurement.
F. Turn the ECS to the STOP position and push in
the emergency stop push button.
G. At the relay module, measure the resistance from
RM-22toRM-7.Makeanoteoftheresistance
measurement.
Expected Result:
The initial resistance m e asurement after removing
the wires from the relay module should be 5000
ohms. The resist an ce measurement shou ld be le ss
than 5 ohms when the ECS is placed in the STOP
position.
Results:
•
OK – The resistance measurements are correct.
The problem does not exist at this time. The
initial problem was probably caused by a poor
electrical connection or a short at one of the
harness connectors that was disconnected and
reconnected. Resume normal operation and watch
for a recurrence. STOP.
•
NOT OK – Either one of the resistance
measurements are NOT correct. The relay module
has failed.
Repair: Replace the relay modu le. refer to Tes t ing
And Adjusting, “Relay Module - Replace”.
STOP.
i02888449
GSC CID 0443 - FMI 12
SMCS Code: 4490-035-R7
Conditions Which Generate This Code:
The GSC+P uses the Crank Terminate Relay (CTR)
as part of the logic to activate the Voltage Build up
Relay (VBR). The C T R is located within th e re la y
module. The governor control switch is located on
the front panel.
The CTR is used t o indicate when the engine is
finished cranking. The GSC+P activates the CTR
when engine speed is greater than the crank
terminate setpoint. (Setpoint P011 should be 400
RPM.) Also, the st artin g motor relay has been
deactivated. The CTR deactivates when the engine
RPM reaches 0.
Note: Whenever the G SC+P activates the CTR, “K3”
is show n on the lower disp lay. When t he CTR is not
activated, “K3” is not shown.
The possible cause of a CID 0443 FMI 12 is an open
coil or a shorted coil of the CTR.
The system responses to this diagnostic code are
listed b elow.
•
IfaCID0443FMI12occursandtheCTRis
activated, the engine will continue to run, but the
Generator Running Relay (GRR) and the governor
control switch are deactivated. On PEEC engines,
the AUX is deactivated.
•
If a CID 0443 FMI 12 occurs and the CTR is not
activated, then the engine is able to start and the
engine is able to run. The GRR is not activated and
the Governor control switch is not activated. On
PEEC engines, the AUX is not activated.
TheGSC+PtreatsaCID0443FMI12asanalarm
fault. Active alarm fault s are shown on the dis pla y
when the “Alarm Codes” key is pressed. Also, the
active alarm faults are shown when the Engine
Control Switch (ECS) is in any p osition e xcept the
OFF/RESET position. Clear the diagnostic code from
the fault log after t roubleshooting is complete.
This troubleshooting p rocedure is used to correct
an active CID 0443 FMI 12 or the troubleshooting
procedure is for an inactive CID 0443 FMI 12.
Test Step 1. CHECK THE STATUS OF THE
DIAGNOSTIC CODE.
A. Turn the ECS to the OFF/RESET position and
then tu rn the ECS to the STOP position.
B. Press the “Alarm Codes” key.