84 KENR8601
Troubleshooting Section
Repair: Program the setpoints in OP8 to match the
values on the ATB+. Refer to System O peration,
“Voltmeter/Ammeter Programming OP8”.
STOP.
Test Step 7. CHECK THE AC OFFSET
ADJUSTMENT
A. Check the AC offset adjustment. Refer to System
Operation, “AC Offset Ad justment OP10 ”.
Expected Result:
The offset values should be set to zero.
Results:
•
YES – The offset values are set to zero.
Repair: The GSC+P may have failed. It is unlikely
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer to Testing And
Adjusting, “EMCP Electronic Control (Generator
Set) - Replace”.
STOP.
•
NO – The offset values are not set to zero.
Repair: Reset the offset values to zero. Refer to
System Operation, “AC Offset Adjustment OP10”.
Verify that the voltage readings are accurate.
STOP.
Te st Step 8. CHECK SETPOINT P021
A. Check the setpoint P021. Refer to Testing and
Adjusting, “Engine/Generator Setpoint Viewing
OP2-0”.
Expected Result:
P021 sh o uld be se t to the same ratio as the curren t
transformers.
Results:
•
OK – P021 setpoint is set to the same ratio as the
current transformers. Proceed to Te st Step 9.
•
NOT OK – P021 setpoint is NOT set to the same
ratio as the current transformers.
Repair: Program P021 tothe same ratio as
the current transformers. Refer to Testing
and Adjusting, “Engine/Generator Setpoint
Programming OP5-0”.
STOP.
Test Step 9. CHECK THE VALUES IN OP8
A. Turn the ECS to the STOP position in order to
shut down the engine. Enter service mode and
enter the password. OP4 is showing on the lower
display. For m ore information, refer to Systems
Operation, “Service Mode”for more information.
Refer to the Systems O p eration, “Password E ntry
OP3”for more information.
B. Press the “SCROLL UP” key five times. “OP 8” is
showing on the lower display.
C. Press the “SCROLL UP” key five times. “OP 8” is
showing on the lower display.
D. Press the “SELECT” key. “AC01” is showing. The
value of the setpoint is also showing. The value
will be between 0 to 255. R ecord the value.
E. Press the “SCROLL UP” key in order to retrieve
the values for setpoints AC02 through AC06.
Record each value.
F. Press the “EXIT” key. “OP 1” is showing on the
lower displa y.
G. Press the “EXIT” key. The display will return to the
Normal M o de .
H. Compare the recorded values with the values that
are written on the bar code sticker of the ATB+.
Expected Result:
The recorded values should match the values that
are written on the bar code sticker of the ATB+.
Results:
•
YES – The values match.
Repair: The GSC+P may have failed. It is u nlike ly
that the GSC+P has failed. Exit this procedure and
perform this entire procedure again. If the problem
remains, replace the GSC+P. Refer to Testing And
Adjusting, “EMCP Electronic Control (Generator
Set)-Replace”.
STOP.
•
NO – The values do NO T match.