KENR8601 143
Troubleshooting Section
Results:
•
OK – The diagnostic code changes to inactive.
Proceed to Test Step 2.
•
NOT OK – The diagnostic code rem ains a ctive.
TheGSC+Pmayhavefailed.
Repair: It is unlikely th at the GSC+P has failed.
Exit this diagnostic code procedure and repeat
the CID 0859 FMI 03 diagnostic code procedure
again. If the cause of the failure is still unknow n ,
then replace the GSC+P.
STOP.
Te st Step 2. CHECK FOR A SHORT TO
“BATT-” IN THE WIRING OF THE kW
LEVEL OUTPUT
A. Shut down the genset.
B. Disco n nect the “BATT-” terminal from the battery.
C. The wire remains disconnected from pin 34 of the
GSC+P.
D. Measure the resistance between the wire that wa s
disconnected from pin 34 of the GSC+P and the
“BATT-” terminal.
Expected Result:
The resistance is greater than 5000 ohms.
Results:
•
OK – The resistance is greater than 5000 ohms.
The resistance is correct.
Repair: The f ailure is in termittent. The probable
cause is a poor electrical connection. Check the
wiring for damage and clean all connections. Exit
this procedure and perform t he CID 0859 FMI 04
procedure again. If no failure is found and the
diagnostic code is still active, replace the GSC+P.
STOP.
•
NOT OK – The resistance is less than 5000
ohms. The resistance is NOT correct. The circuit
is shorted.
Repair: Repair the wiring between pin 34 of the
“BATT-” terminal.
STOP.
i02890649
GSC CID 1038 - FMI 03
SMCS Code: 1264-035
Conditions Which Generate This Code:
The output of the “Speed Adjust 1” provides
an analog signal that is being used to vary the
engine speed in order to match the phase of the
generator to the phase o f the bus. The full output
voltage is approximately −5.0to+5.0DCV.Ifthe
synchronization is disabled, the output will be 0.0 ±
0.5 DCV.
Note: Setpoint P308 must be set to a value that is
greater than zero in order for this proced ure to be
completed. This se tpointcanbeavaluefrom0to
100. The factory default is 50. Refer to Systems
Operation, “Parallel Setpoint Programming” for more
information.
The possible cause of a CID 1038 FMI 03 is a short
from the output signal of the “Speed Ad just 1” to the
positive terminal of the battery (“B+”).
A CID 1038 FMI 03 is detected when the GSC+P is
NOT activating the output of the “Speed Adjust 1”.
TheGSC+PtreatsaCID1038FMI03asanalarm
fault. The synchronization process w ill be stopped
until the diagnostic code is cleared and the diagnostic
code is corrected.
Test Step 1. CHECK TH E INACTIVE
VOLTAGE LEVEL OF TH E OUTPUT OF
THE “SPEED ADJUST 1”.
A. Turn the E ngine Control Switch (ECS) to STOP.
B. Locate the wire that is connecting pin 27 of the
GSC+P to terminal 24 of the Load Share Module
(LSM). Pin 27 of the GSC+P will remain connected
to the wire.
C. Useacableprobetomeasurethevoltageonpin
27 of GSC+P.
Expected Result:
The voltage should measure 0.0 ± 1.0 DCV.
Results:
•
OK – T he voltage level is 0.0 ± 1.0 DCV. Procee d
to Test Step 2.
•
NOT OK – The voltage level is below the correct
range or the voltage level is above the correct
range.