68 KENR8601
Systems Operation Section
When an input that is corresponding to one of the red
indicators is ac tiva ted, the indicator will flash and the
horn will sound. When the input is disconnected from
the battery n egative termi na l, the horn w ill continue
to sound and the red indicator will continue to flash
until the alarm silence switch is pressed.
When an inpu t th at is corresponding to one of the
amber indicators is activated, the indicator will flash
but the horn does NOT sound. When the input is
disconnected from the battery negative terminal, the
amber indicator will turn off.
Alarm Silence Function
The alarm silence switch is activated by connec tin g
the corresponding input to the battery negative
terminal.
When an input is connected to the battery negative
terminal, activating the alarm silence switch ca uses
the horn to cease. The indicator stops flashing and
the indicator changes to being ON continuously.
The alarm silence function will be overridden if the
following event occurs. The status of any of the eight
switched inputs change. The change of status will
causeadditionalinputstobeclosedtothebattery
negative terminal.
The Alarm Silence Function w ill not be overridden
if the change in status is the opening of any of
the inputs fro m the battery neg ative terminal. The
indicators will turn OFF when the corresponding input
is disconnected from the battery negative terminal.
Lamp Test Function
Activating the “Lamp Test” switch results in sounding
the horn and turning on a ll indicators continuously
for 10 seconds or until the switch is dea ctivated.
The“LampTest”inputcanbewiredtotheswitchof
another alarm module.
Customized Labeling
The condition that is being monitored by each
indicator is det ermined by the cu st omer. The
130-3326 Film provides a wide variety of labels in
order to customize the CAM to an application.
i02899482
Customer Interface Module
SMCS Code: 4490
g00328626
Illustration 48
Customer Interface Module (CIM)
(1) Relay Board
(2) Electronic Control
Refer to Testing And Adjusting, “Sc he m at ics And
Wiring D iag ram s” for more information ab o ut the
Customer Interface Module (CIM).
The CIM provides an interface between the GSC+P
and the customer in the form of dry contacts.
Separate relay contacts are the interface that is
between the GSC+P and the switchgear. The two
major components of CIM are the relay board (1) and
the electronic control (2). The electronic control (2)
and the alar m annu nciator conn e c t to the same serial
data link. The ope ra tion of the CIM is simila r to the
operation of the alarm annunciator. The information
on the data link is decoded into discrete outputs. The
outputs then drive the relays that are located on the
relay board (1). The relay contacts can be used to
soundahorn.Therelaycontactscanbeusedtoflash
a lamp or the relay c ontacts c an be used to trigger
another procedure. Once an output is activated, the
output remains energized until the faults that initiated
the alarm are cleared. All electronic control outputs
cycle at 0.5 Hz if a malfunction in the serial data link
occurs. This includes the relays as well. The CIM is
designed for operation when the CIM is powered by a
battery system that supplies 24 DCV. The CIM is also
designed for operation when the CIM is powered by
a battery system that supplies 32 DCV.
The available serial data link information is listed
below.
•
High coolant temperature alarm
•
Low oil pressure alarm
•
Low coolant temperature alarm