KENR8601 35
Systems Operation Section
3. Press “SELECT” key. “P001” is showing for OP2-0
which is followed by the va lu e of the setpoint.
“P101” is showing for OP2-1 w hic h is followed
by the value of the setpoint. The ten digit serial
number is showing on the display for OP2-2.
4. Press the “SCROLL UP” key or the “SCROLL
DOWN” key. The next setpoint value is showing.
Repeat this step until all the desired setpoints and
the setpoint values are viewed.
5. Press “EXIT” key. “OP1” is showing on the lower
display.
6. Press “EXIT” key. The display returns to the
normal mode.
i02882853
Parallel Setpoint Viewing
OP2-3
SMCS Code: 4490
OP2-3 is the option for Parallel Setpoint Viewing.
The Parallel setpoints define various parameters that
allow precise frequency and phase matching. The
setpoints from P301 to P314 are programmable. For
a description of these setpoints, see Testing And
Adjusting, “Parallel S et po int Prog ra mming OP5-3”.
i02898181
Password Entry OP3
SMCS Code: 4490
OP3 is the option for entering the password that is
required for accessing OP4 through OP11. Options
for the service modes OP4 through OP11 are
protected with passwords. The passwords reduce the
possibility of mis takenly altering inform ation . Options
OP1 and OP2 are used to view information. OP1 and
OP2 are not protected with passwords.
The “SCROLL” keys must be actuated in the
correct s equence in order to gain access to OP4
through OP11. The password is identical for every
GSC+P. The password cannot be changed. After the
password is entered, the OP4 through OP10 options
can be accessed. If a mistake is made during the
entry of the password, “PE FAIL” is brieflyshown
on the upper display. The operator can restart the
process of entering the password by pressing the
“SELEC T” key.
Procedure To Enter The Password
Note: Service mode cannot be entered when the
Engine Control Switch (ECS ) is in the “AUTO”
position.
Note: Any active shutdo w n fault must be made
inactive in order to access Service Mode. A shutdown
fault is active if the shutdown indicator for the fault is
FLASHING. To temporarily change a shutdown fault
from an active shutdown fault to an inactive shutdown
fault, turn the ECS to the OFF/RESET position. To
permanently change a shutdown fault from an active
shutdown fault to an inactiv e shutdow n fault, the
fault must not be occurring. Also, the ECS must be
turned to the OFF/R ESET position. If the jumper from
terminal 6 to terminal 9 is not installed on the ECS,
the GSC+P will not power up in OFF/RESET and
any active shutdown fault must be corrected before
entering Service Mode.
1. Press “Service Mode” key in order to enter service
mode. “OP1” is showing on the lower display.
Refer to Systems Operation, “Service Mode ” for
more information.
2. Press the “SCROLL UP” key four times.“OP3” is
showing.
3. Pressthe“SELECT”key.“PE_____”is
showing on the display. The first dash is flashing.
4. Press “SCROLL RIGHT” key. “P E 1 _ _ _ _”
is show ing on the display. The second dash is
flashing.
5. Press“SCROLLDOWN”key.“PE13___”is
showing on the display. The third dash is flashing.
6. Press “SCROLL UP” key. “P E 1 3 2 _ _”is showing
on the display. The fourth dash is flashing.
7. Press“SCROLLDOWN”key.“PE1323_”is
showing on the display. The fifth da sh is flashing.
8. Press“SCROLLRIGHT”key.“PE13231”is
showing.
9. Press “ENTER” key. “P E PASS”is show ing.
10. Press “ EXIT” key. OP 4 is showing.
Note: Once the password is entered, any option can
be acce ssed. The password remains activated until
Service Mode is ex ite d.