14 KENR8601
Systems Operation Section
•
Left side exhaust temperature (optional)
•
Right side exhaust temperature (optional)
•
Engine oil temperature (optional)
•
System battery voltage
•
Engine hours
•
Engine speed
•
Engine oil pressure
•
Engine coolant temperature
Note: If the GSC+P displays dashes (---) for
oil pressure, coolant temperature, or engine oil
temperature, this indicates that the GSC+P is
receiving in valid data from the sensor. The upper
display will be showing a corresponding diagnostic
code for the sensor. Refer to th e appropriate
procedure in Troubleshooting, “Troubleshooting
Diagnostic Codes”.
The value for one of these conditions is shown on
the display for two seconds. The display then scrolls
to the value for the next condition. A small pointer
identifies the e ngine condition that corresponds to
the value that is showing. When the engine meter
key is pressed, the lower display (6) stops s crolling.
The lower display continuously shows one particular
value. The pointer flashes above the value that is
showingonthedisplay.
g00394569
Illustration 23
Lower Display Showing:
K1, K3 and K5
are active.
K2, K4, K6, K7 and K8 are not active.
The relay status indicators are on the bottom of the
lower display. When a GSC+P relay is activated, the
correspon
ding indicator (K1, K2, etc) is sho w n on
lower display (6). When a relay is not activated, the
corresponding indicator (K1, K2, etc) is not shown.
Keypad
g00395398
Illustration 2
4
Keypad (7) for the EMCPII+P Control Panel
Keypad (7) is used to control the information that is
shown on upper display (5) and lower display (6).
The seven keys
have two sets of functions, normal
functions and s ervice functions. Refer to the t opic
Systems Operation, “Service Mode” for a description
of the service
functions of the keys. The normal
functions of the keys are described in the following
paragraphs.
Power Meter Key – This key controls the viewing o f
power meter info rmation. This information is shown
on the lower d
isplay. Pressing the key for at least five
seconds causes all the power meter data to scroll
once. The default power meter data then resumes
scrolling.
Briefly pressing this key (for less than five
seconds) will stop the scrolling of t he powe r me te r
functions until the key is pressed again.
AC Meter Key – The A C meter key controls the
viewing of the AC parameters on the upper display.
Pressing t
he key causes the display to sho w a
different set of parameters.
Engine Met
er Key – This key contro ls the viewing
of engine parameters on the lower display. Pressing
the key stops the scrolling of engine conditions. The
value for o
ne particular engine condition will show
continuously. The pointer flashes indicating that
the scrolling is stopped. The scrolling of th e engine
conditio
ns will resume when the engine meter key is
pressed again.
Lamp Test
Key – Pressing this key performs a lamp
test on the GSC+P and the optional alarm module.
On the GSC+P, the ten fault indicators are ON
CONTINU
OUSLY. Every segment of upper display
(5) and lower display (6) are ON. On the optional
alarm module, all of the indicators are ON and the
horn sou
nds. The lamp test function automatically
turns off if an operator presses the key and holds the
key for longer than ten s econds.