Systems Operation Section
(Table 9, contd)
OP6-0 Setpoints
(1)
- Spare Input/Output Programming
Setpoint
Name Description
Range Of Value Factory Default
SP13 Spare Output
Response
GSC+P respo nse
to the s pare out
put
trigger cond ition.
0-activelow
1 - active high
0
SP15 Spare Relay Output
Response
GSC+P response to
the spare relay trigger
condition.
0 - relay inactive when
triggered
1 - relay active when
triggered
1
SP14 Spare Output Trigger
Condition
The conditio n u
sed by
the G SC+P to trigger
the spare output
trigger respo
nse.
SP16 Spare Relay Output
Trigger Condition
The conditio n used by
the G SC+P to trigger
the spare rela
y.
0 - unused
1-activeSP01fault
(2)
2-activeSP02fault
(2)
3-activeSP03f
ault
(2)
4-activeSP04fault
(2)
5 - a ny c ombination
of active SP01,
SP02,
SP03 or SP4 faults
(2)
6 - any active
shutdown fault
(AL1 -
AL14, SP01 - SP04, o r
CID FMI)
7 - any active al
arm or
shutdown fault (AL1 -
AL15, SP01 - SP04, o r
CID FMI)
8 - cooldown mode
9 - coolant loss fault
(2)
10 - high oil
temperature fault
(2)
11 - CCM control
(3)
8
SP17 Spare Indicator 1
Trigger Condition
The conditio n u
sed by
the G SC+P to trigger
spare indicator 1.
SP18 Spare Indicator 2
Trigger Condition
The conditio n u
sed by
the G SC+P to trigger
Spare Indicator 2.
SP19 Spare Indicator 3
Trigger Indicator
The conditio n
used by
the G SC+P to trigger
spare indicator 3.
0 - unused
1-activeSP01fault
(2)
2-activeSP02fault
(2)
3-activeSP03fa
ult
(2)
4-activeSP04fault
(2)
5 - a ny c ombination
of active SP01,
SP02,
SP03 or SP04 faults
(2)
6 - coolant loss fault
(2)
7 - high oi l tempe
rature
fault
(2)
8 - kW level relay
active
0
(1)
The setpoints ar
e programmed at the factory to the default value. The setpoints may be changed to satisfy customer requirements
or application r
equirements.
(2)
Either alarm or shutdow n faults are valid trigger conditions.
(3)
When SP14 is programmed to 11 (CCM control), the spare output is always active low. W hen SP16 is programmed to 11 (CCM control),
the spare relay is always active when triggered.
i02898711
Hourmeter Programming OP7
SMCS Code: 4490
OP7 is used in order to program the hours that are
on the hour mete
r.
Note: The value for the hour meter on the GSC+P
displayisdete
rmined by the engine ECM. The OP7
is not available for programming.