36 KENR8601
Systems Operation Section
i02898183
Fault Log Clearing OP4
SMCS Code: 4490
Fault Log Clearing OP4
OP4 is the option for clearing an inactive fault from
the fault log of the GSC+P. After a diagnostic fault is
investigated and/or the fault is corrected, the fault
should be cleared from the fault log. Fault log clearing
helps prevent confusion during future service calls.
After all diagnostic faults are cleared and the GSC+P
is in normal mode, the “DIAG” indicator is not shown
on the upper display. Refer to S ystems Operation,
“Fault Lo g Viewing OP1” for more information.
Procedure for Clearing Faults
Note: Service Mode cannot be entered when the
Engine Contro l Switch (ECS) is in the AUTO position.
Note: An active shutdown indicator will be
FLASHING. Active shutdown indicators must be
deactivated in order to access the service mode. To
temporarily change a shutdown fault from an active
shutdown fault to an inactive shutdown fault, turn
the ECS to the OFF/RESET position. Permanently
changing a shutdown fault from an active shutdown
fault requires correcting the active shutdown fault.
The ECS must be turned to the OFF/RESET position.
If the jumper from terminal 6 to terminal 9 is not
installed on the ECS, the GSC+P does not power up
in OFF/RESET. Any active shutdown fault must be
corrected before the service mode is entered.
1. TurntheECStotheSTOPpositioninordertoshut
down the engine. Enter service mode and enter
the password. “OP 4” is showing on the lower
display. Refer to System s Operation, “Password
Entry OP3” for more information on entering the
password.
2. Press “SELECT” key. A CID FMI fault code is
showing and the number of occurrences are
showing. The lower display shows the hour meter
reading of the first occurrence of the fault and the
last occurrence of the fault.
3. Press “SELECT” key. The C ID FMI fault code,
hour meter reading, and fault count will fl ash.
4. Press and hold the “EN TER” key for t wo s econds.
If there is only one CID FMI fault code, the CID
FMIfaultthatwasflashing disappears and the
upper display is blank except for the flashing
“SERV” indicator. “OP1” is showing on the lower
display. Proceed to the next step. If there is more
than one CID FMI fault code, the CID FMI that was
flashing disappears. The upper display shows the
next CID FMI fault code, the fault count, and the
hour meter reading. Repeat steps 3 and 4 until all
faults are erased. Th e lower display then shows
OP 1. Proceed to Step 5.
5. Press the “EXIT” key. “OP 1” is showing on the
lower displa y.
6. Press the “EXIT” key. The display is now in normal
mode.
i02898192
Engine/Generator
Programming OP5-0
SMCS Code: 4490
OP5-0 is the option for programming the
engine/generator setpoints. The engine/generator
setpoints affect the proper operation and serviceability
of the engine, and the accuracy of information shown
on the display. The setpoints are programmed in the
GSC+P at the factory.
The setpoints may require changing when the
GSC+P is moved from one engine to another engine.
The setpo in ts may also require cha n gin g in order to
satisfy the customer’s requirements. The setpoints
that are stored in the GSC+P must match the
specified setpoints of the particular generator set.
The setpoints are P001 to P033 and the setpoints are
programmable. The setpoints are described in the
OP5-0 Setpoints. Refer to Table 6.
Procedure For Engine/Generator
Programming
Note: Service Mode cannot be entered when the
Engine Control switch (EC S) is in the AUTO position.