40 KENR8601
Systems Operation Section
(Table 6, contd)
OP5-0 S etp oints
- Engin e/Generator Programming
(1)
Setpoint
Name Description
Range Of Value Controller Default
P027
Shutdown
Override
For High Oil
Temperature
Fault
GSC+P r esponds to an engine high oil
temperature fa
ult. (Determined by application
or customer.)
0 - alarm on ly
(shutdown override,
no engine shutdown)
1 - engine shutdown
0
P028 Nameplate
Voltage
Rated voltage of the generator. This s etpoint
is used for protective relaying functio ns.
100V to 25kV
in increments of 1
480V
P029 Nameplate
Current
Rated current
output of th e generator.
0 to 4000A
in increments of 1
600A
P030 Nameplate
Power
Rated power capability of the generator.
0 through 10MW
in increments of 1kW
400kW
P031 Rated
Frequency
Nominal frequency ratin g of ge nerator set.
50, 60 or 400Hz 60Hz
P032
Connection
Configuration
Of Generator
Wye or delta co
nfiguration of generator.
0-wye
1 - delta
0
P033
(8)
Number Of
Generator Poles.
Number of generator poles.
0 through 254
in increments of 2
4
(1)
The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular generator set.
(2)
The defaults shown represent the defaults in the GSC+P controller. Setpoints will be changed at the factory for specific generator set
applications.
(3)
When oil pressure drops to within 34 kPA (5 psi) of the “P013” or “P014” setpoint, a low oil pressure alarm is issued by the G S C+P an d the
optional alarm m odule (with the exception of the NFPA 99 RAN).
(4)
When coolant temperature rises to within 6°C (11°F) of the “ P015 ”setpoint, a high water te mperatu re alarm is issued by the GSC+P and
the optional alarm module (with the excep tion of the NFPA 99 RAN).
(5)
The values other than the defau lt (700V) are for switchgear applications and require the use of external potential transformers and the
removal of the AC voltage range jumper located in the relay module. Refer to Testing And Adjusting, “AC Voltage Range Selection”.
(6)
After setpoint P022 is reprogrammed, the GSC+P must be power cycled (powered down a nd then powered up).
(7)
The P 024 setpoint only functions when the P023 setpoint is set to 1 (gas engine).
(8)
When P033 is programmed to 0 poles, the AL15 fault (GSC+P Configuration Error) is disabled.
i02898415
Protective Relaying
Programming OP5-1
SMCS Code: 4490
Protective Relaying Programming
OP5-1 is the option for the programming of the
protective relaying setpoints. When one or more of
the protect ive relay functions occur, the protec tive
relaying setpoints determine the response of the
GSC+P. The GSC+P provides the protective relaying
function in order to reduce the pos sibility of dam age
to the generator. The protective relaying functions
are used in order to reduce the possibility of dama ge
to the customer equipment. The setpoints are
programmed in the GSC+P at the factory to the
default values. The setpoints m ay be changed in
order to satisfy the requirements of the customer. The
setpoints are from P101 to P142 and the setpoints
are programmable. Each of the setpoints is described
in Table 7.
Procedure For Protective Relaying
Programming
Note: ServiceModecannotbeaccessedwhenthe
Engine Control Switch (ECS) is in the AUTO position.
Note: An active shutdown fault is indicated by a
FLASHING shutdown indicator . An active shutdown
fault must be made inactive in order to a ccess service
mode. To temporarily change a shutdown fault from
an active shutdown fault to an inactive shutdown
fault, the shutdown fault must no longer be occurring.
The fault must be co rrected. Th e ECS mu st be
returned to the OFF/RESET position. If the jumper
fromterminal6toterminal9isnotinstalledonthe
ECS, the GSC+P does not power up in OFF/RE SET
and any active shutdown fault must be corrected
before entering service mode.
1. TurntheECStotheSTOPpositioninordertoshut
down the engine. Enter service mode and enter
the password. “OP 4 ” is showing on the lower
display. For more information, refer to System
Operation, “Password Entry OP3”.