KENR8601 15
Systems Operation Section
Alarm Codes K ey – If fault alarm indicator (4) is
FLASHING, pressing this key causes upper display
(5) to show the corresponding alarm fault code.
Pressing this key again will resume the showing of
generator AC output information on the upper display
(5). If fault alarm indicator (4) is OFF, this key has no
function. For more information on alarm fault codes,
refer to Systems Operation, “Fault Description”.
Exit Key – This key only functions when the GSC+P
is in Service Mode. Re fer to Syste ms Operation,
“Service Mode”.
Service Mode Key – Pressing this key causes the
GSC+P to enter service m ode. Refer to Systems
Operation, “Service Mode” for more information.
Relays
g005214
82
Illustration 25
Relay Module On Rear Of GSC+P
g00436699
Illustra
tion 26
Relays In Relay Modu le
(1) Jumper block
The relay
s are located in the relay m o d ule o n the
rear of the GSC+P. The relays are permanently
attached within the relay m odule. The relays are
not remo
vable. The entire relay module is replaced
if a relay has failed. For more information, refer to
Schematics And Wiring Diagrams, “Generator Set
Wiring D
iagram”.
Some o f the con tacts of the relays are internally
connec
ted to the terminals of the relay module. The
contacts are available fo r the customer’s use . The
voltage specifications and the current specifications
for eac
h terminal of the relay are listed in the following
chart.
Note: J
umper block (1) is used to select the voltage
range of the voltmeter of the G S C+P. Jumper block
(1) is installed for systems w ith 7 00 v olts full scale AC
input
s. Jumper block (1) is NOT installed for systems
with 150 volts full scale AC inputs or for any unit w ith
external potential transformers. The relay module
comes
factory equipped with the jumper block (1)
installed. Refer to Testing And Adjusting, “AC Voltage
Range Selec tio n”.