76 KENR8601
Troubleshooting Section
Repair: The GSC+P Relay Module may have
failed. It is unlikely that the GSC+P Relay Module
has failed. Exit this procedure and perform this
entire procedure again. If the problem remains,
replace the GSC+P Relay Module. Refer to Testing
And Adjusting, “EMCP Electronic Control (Relay
Module) - Replace”.
STOP.
•
NOT OK – The engine runs and the engine will
start. Proceed to Test Step 6.
Te st Step 6. CHECK THE SYSTEM BY
USING THE ESPB.
The engine remains running and the red fault
shutdown indicator is FL ASHING.
A. Push the Emergency Stop Push Button (ESPB).
Expected Result:
The engine should shut down.
Results:
•
OK – The engine does shutdown. Proceed to Test
Step 7.
•
NOT OK – The engine does NOT shut down.
Repair: The engine’s ECM may have failed. Refer
to Service Manual, RENR9968 or Service Manual,
RENR9348.
STOP.
Te st Step 7. CHECK THE WIRING
BETWEEN THE ENGINE’S ECM AND THE
GSC+P.
The engine remains running and the red fault
shutdown indicator is FL ASHING.
A. Check the wiring between RM-14 of the GSC+P
and J1-40 on the engine’s ECM. Check for shorts,
open connections, or damaged wires.
Expected Result:
The w iring has a shorted connection, an open
connection, or the wiring is damaged.
Results:
•
OK – The wiring is damaged.
Repair: Troubleshoot and repair the wiring. Refer
to Generator Set Wiring Diagram in Testing And
Adjusting, “Schematics And Wiring Diagrams”.
Verify that the repair corrects the problem.
STOP.
•
NOT OK – The wiring is not damaged at all. The
engine’s ECM may have failed.
Repair: The engine’s ECM may have failed. Refer
to Service Manual, RENR9968 or Service Manual,
RENR9348.
STOP.
i02902638
Display of Voltage or Current
Is Zero
SMCS Code: 4490-035
System Operation Description:
Zero volts or zero amperes are showing on the
display of the GSC+P for one or more AC phases.
This is showing while the genset is running and the
load is connected.