KENR8601 131
Troubleshooting Section
•
IfaCID0446FMI12occursandtheASRisnot
activated, then there is no immediate effect on the
system. The engine is able to start and the engine
is able to run.
•
IfaCID0446FMI12occursandtheASRisnot
activated, then the ASR cannot energize the air
shutoff solenoid when a s hutdown fault occurs.
This troubleshooting procedure is for an active CID
0446 FMI 12 or the troubleshooting procedure is for
an inactive CID 0446 FMI 12.
Te st Step 1. CHECK T HE STATUS OF THE
DIAGNOSTIC CODE.
A. TurntheEngineControlSwitch(ECS)tothe
OFF/RESET posit ion an d th en turn the ECS to
the STOP position.
B. Press the “Alarm Codes” key.
C. Ob serve the upper display. Check that the CID
0446 FMI 12 is active.
D. If the diagnostic code is not active, enter the
Service Mode. View the fault log for a OP1. Check
that th e diagnostic code is in active.
Expected Result:
A CID 0446 FMI 12 is dis pla yed as an a ctive
diagnostic code or CID 0446 FMI 12 is displayed as
an inactive diagnostic code.
Results:
•
OK – The CID 0446 FMI 12 is active or the CID
0446 FMI 12 is inactive. Proceed to Test Step 2.
•
NOT OK – The CID 044 6 FMI 12 has not occurred.
The diagnostic c ode is not active and the diagnostic
code is not inactive. STOP.
Te st Step 2. CHECK THE INTERNAL
CABLE OF THE RELAY MODULE.
Note: Only open the relay module in a dry
environment. If the inspect ion and repair t akes more
than approximately twenty minutes replace the
desiccant bag in the GSC+P housing. See Testing
And Adjusting, “Relay Module - Replace”.
A. Turn the ECS to the OFF/RESET position.
B. Disconnect the negative battery cable.
C. Temporarily, remove the relay module from the
GSC+P. Refer to Testing And Adjus tin g, “Relay
Module - Replace”.
D. Check the cable that attaches the relay module
to the GSC+P.
Expected Result:
The cable should be firmly seated in the connector.
The clamp should be in place. The cable should not
be damaged.
Results:
•
OK – The cable is firmly seated in the connector.
The clamp is in place. The cable is not damaged.
Reassemble the relay module to the GSC+P.
Proceed to Test Step 3.
•
NOT OK – One or more of the components are
damaged or the components are missing.
Repair: Replace the clamp if the clamp is missing.
If the cable is damaged, replace the GSC+P. Refer
to Testing and Adjusting, “EMCP Electronic Control
(Generator Set) - Replace”.
STOP.
Tes t Step 3. PERFORM A FUNCTIONAL
CHECK O N THE ASR.
A. Turn the ECS to the OFF/RESET position.
B. Reconnect the negative battery cable.
C. Disconnect all wires from RM-19 and RM-5 of the
relay module.
D. Remove fuse “F3” from the relay module.
E. At the relay module, measure the resistance from
RM-19 to RM-5. Make a note of the resistance
measurement.
F. TurntheECStotheSTOPpositionandpush
in the Emergency Stop Push Button (ESPB).
Measure the resistance from RM - 19 to RM -5.
Make a note of the resistance measurement.
Expected Result:
The initial resistance measurement after removing
the wires and the fuse from the relay module
should be greater than 5000 ohms. The resistance
measurement should be less than 5 ohms when the
ECS is placed in the STOP position.
Results:
•
OK – The resistance measurements are correct.
The problem does not exist at this time. The
initial problem was probably caused by a poo r
electrical connection or a short at one of the
harness connectors that was disconnected and
reconnected. Resume normal operation and watch
for a recurrence. STOP.