130 KENR8601
Troubleshooting Section
B. Reconnect the negative battery cable.
C. Disconnect all wires from RM-23 and RM-24 of
the relay module.
D. Rem o ve fuse “F6” from the r elay module.
E. At the relay module, measure the resistance from
RM-24toRM-8.Makeanoteoftheresistance
measurement.
F. At the relay module, measure the resistance from
RM-23toRM-9.Makeanoteoftheresistance
measurement.
Expected Result:
The resistance measurement from RM-24 to RM-8
should be greater than 5000 ohms. The resistance
measurement should be less than 5 ohms at RM-23
to RM -9.
Results:
•
OK – The resistance measurements are correct.
The problem does not exist at this time. The
initial problem was probably caused by a poor
electrical connection or a short at one of the
harness connectors that was disconnected and
reconnected. Resume normal operation and watch
for a recurrence. STOP.
•
NOT OK – Either one of the resistance
measurements are NOT correct. The relay module
has failed.
Repair: Replace the relay module. Refer to Testin g
And Adjusting, “Relay Module - Replace”.
STOP.
Te st Step 4. FUNCTIONAL CHECK
OF THE RUN RELAY IN THE START
POSITION
A. Turn the ECS to the START position .
B. The wires from RM-23 and RM-24 remain
disconnected.
C. At the relay module, measure the resistance from
RM-23toRM-9.Makeanoteoftheresistance
measurement.
D. Measure the resistance from RM-24 to RM-8.
Make a note of the resistance measurement.
Expected Result:
TheresistancemeasurementfromRM-23toRM-9
should be greater than 5000 ohms. The resistance
measurement should be less than 5 ohms at RM-24
to RM -8.
Results:
•
OK – The resistance measurements are correct.
The problem does not exist at this time. The
initial problem was probably caused by a poo r
electrical connection or a short at one of the
harness connectors that was disconnected and
reconnected. Resume normal operation and watch
for a recurrence. STOP.
•
NOT OK – Either one of the resis tance
measurements are NOT correct. The relay module
has failed.
Repair: Replace the relay module. Refer to Testing
And Adjusting, “Relay Module - Replace”.
STOP.
i02888508
GSC CID 0446 - FMI 12
SMCS Code: 4490-035-R7
Conditions Which Generate This Code:
The Air Shutoff Relay (ASR) is no t used on the C 3 2
EMCP II+P. Air shutoff is controlled by the engine’s
Electronic Control Module (ECM). The ASR is located
within the relay module. The air shutoff solenoid is
located within the air inlet system of the engine.
The GSC+P activates the ASR for some active
shutdown f au lts.
Note: Whenever the GSC+P activates or the GSC+P
attempts to activate the ASR , “K6” is shown on the
lower display. When the ASR is not activated, “K6” is
not shown.
The possible cause of a CID 0446 FMI 12 is an open
coil or a shorted coil of the ASR.
The system responses to this diagnostic code are
listed b elow.
•
IfaCID0446FMI12occursandtheASRis
activated, then the system is not affected. The
system is not affected because the air shutoff
is already operating and shutdown mode is
functioning.