116 KENR8601
Troubleshooting Section
Te st Step 1. CHECK IF THE DIAGNOSTIC
CODE IS ACTIVE
A. TurntheEngineControlSwitch(ECS)tothe
OFF/RESET posit ion an d th en turn the ECS to
the STOP position.
B. Press the “Alarm Codes” key.
C. Observe the upper display for a CID 0333 FMI 04.
The diagnostic c ode is a ctive if the upper display
shows a CID 0333 FMI 04.
D. If the diagnostic code is not showing, enter the
service mode and view the fault log. Check the
upper display if the diagnostic code is active.
Expected Result:
A CID 0333 FMI 04 is active.
Results:
•
OK – A CID 0333 FMI 04 is active. Proceed to
Test Step 2.
•
NOT OK – A CID 0333 FMI 04 has not occurred.
The diagnostic code is NOT active. STOP.
Test Ste p 2. CHECK THE GSC+P.
A. Disconnect the cable on the “BATT-” terminal of
the battery or open the optional battery disconnect
switch.
B. Disconnect the data link wire from pin 35 of the
GSC+P.
C. Reconnect the cable on the “BATT-” terminal of
the b attery or close the optional battery disconnect
switch.
D. Turn the ECS to the S TOP position.
Expected Result:
The CID 0333 FMI 04 is inactive.
Results:
•
OK – The CID 0333 FMI 04 is inactive. Proceed
to Test Step 3.
•
NOT OK – The CID 0333 FMI 04 remains active.
TheGSC+Pmayhavefailed.
Repair: The GSC+P may have failed. It is u nlike ly
that the GSC+P has failed. Exit this procedure and
perform this procedure again. Replace the GSC+P
if the CID 0333 FMI 04 remains active. R efer to
Testing and Adjusting, “EMCP Electronic Control
(Generator Set) - Replace”
STOP.
Test Step 3. CHECK THE ALM AND DATA
LINK WIRE
A. The data link wire remains disconnected from the
GSC+P.
B. Disconnect the cable on the “BATT-” terminal of
the battery or open the optional battery disconnect
switch.
C. Disconnect th e da ta link wire from termina l 2 of
the Alarm module.
D. Measure the resistance from the data link wire to
the negative battery terminal on the GSC+P.
Expected Result:
The resistance should be greater than 5000 ohms.
Results:
•
OK – The resistance is greater than 5000 ohms.
Proceed to Test Step 4.
•
NOT OK – The resistance is NOT greater than
5000 ohms. The data link wiring is faulty.
Repair: Use the system schematic in order to
troubleshoot and repair the harness wiring that has
failed between t he ALM and the G S C+P. Refer
toTesting And Adjusting, “Schematics and W iring
Diagrams”.
STOP.
Test Step 4. CHECK THE ALARM
MODULE.
A. The cable on the “BATT-” battery terminal remains
disconnected or the optional battery disconnect
switch is open.
B. The data link wire remains disconnected.
C. Meas ure the resistan ce from term ina l 2 of the
ALM to “BATT-”.
Expected Result:
The resistance should be greater than 5000 ohms.