88 KENR8601
Troubleshooting Section
•
Check The Type Of Wire Or Cable On The
Remote Modules. Three separate wires for the
following connections are recommended for remote
installations: The positive battery wire (“BATT+”),
the negative battery wire (“BATT-”), and the data
for the alarm. Other wires for the switched inputs
on a remote annunciator may also be required by
the application. The wires should be size 16 AWG.
Verify that the w ire is NOT a shielded type. Verify
that the wire does not have twisted conductors.
This type of cable is not appropriate for this
purpose. These types of cables usually have more
capacitance than separate wires and the data from
theGSC+Pcanbecorrupted.
•
Verify The Methods Of Wiring. Each remote
annunciator must have a separate set of three
wires between it and the GSC+P.. Do NOT connect
any wires directly between remote annunciators.
The wires should NOT be in the same conduit as
wires for AC voltage or other high voltage signals.
Test Step 1. CHECK THE DATA CIRCUIT
WIREFORANOPEN
A. Clear the GSC+P Fault Log. R efer to Systems
Operation, “Fault Log Clearing OP4”.
B. TurntheEngineControlSwitch(ECS)to
OFF/RESET.
C. Temporarily connect terminal 1 to terminal 2 of the
alarm module for a few seconds.
D. Temporarily connect terminal 7 to terminal 2 of the
alarm module for a few seconds.
Expected Result:
The CID 333 FMI 03 and CID 333 FMI 04 diagnostic
codes should be temporarily active while the faults
areoccurring.TheCID333FMI03andCID333
FMI 04 diagnostic codes should be contained in the
GSC+P fault log.
Results:
•
OK – The diagnostic codes occur and the codes
are contained in the GSC+P fault log. The GSC+P
and the wire for the alarm (data) have not failed.
Proceed to Test Step 2.
•
NOT O K – The diagnostic codes do NOT occur
and the codes are not in the GSC+P fault log. The
wire from contact 35 of the GSC+P to terminal 2 of
the alarm module is open or the wire has failed.
Also, the GSC+P may have failed. Proceed to Test
Step 3.
Test Step 2. CHECK THE ALARM
MODULE FOR FAULTS.
A. The in dicators on the alarm module remain
flashing.
B. Disconnect the wire on terminal 2 of the alarm
module.
C. Measure the DC voltage from termina l 2 to
terminal 7 of the alarm module.
Expected Result:
The voltage should be 10.5 ± 1.0 DCV.
Results:
•
OK – The voltage is 10.5 ± 1.0 DCV. The
requirements for the alarm module that w ere listed
at the beginning of this procedure may not be met.
Repair: Review the list of requirements at the
beginning of this procedure. If all requirements
are being met, replace the alarm module. If the
problem is not solved, replace the GSC+P. Refer
to Testing and Adjusting, “EMCP Electronic Control
(Generator Set) - Replace”.
STOP.
•
NOT O K – The voltage is NOT 10.5 ± 1.0 DCV.
The alarm module ha s faile d.
Repair: Replace the alarm m odule.
STOP.
Tes t Step 3. CHEC K THE GSC+P FOR
DIAGNOSTIC CODES.
A. Install a cable probe on pin 35 of the GSC+P
40-pin connector. Ensure that the cable probe is
fully se ated.
B. Turn the ECS to the STOP position.
C. Temporarily connect pin 35 of the GSC+P to
“BATT+” for a few se conds.
D. Temporarily connect pin 35 of the GSC+P to
the negative battery terminal “(BATT-)” for a few
seconds.
Expected Result:
The CID 333 FMI 03 and CID 333 FMI 04 diagnostic
codes will temporarily be active on the GSC+P
display while the diagnostic co d es are occurring.